background image

M3LU

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-2652-A  Rev.2  P. 6 / 9

 

OUTPUT TYPE (SW2 & 1) 

Table 10

OUTPUT

SW2-8

SW2-7

SW1-4

SW1-3

SW1-2

SW1-1

0 – 20 mA

OFF

OFF

OFF

ON

OFF

OFF

-2.5 – +2.5 V

OFF

ON

ON

OFF

OFF

ON

-10 – +10 V

ON

OFF

ON

OFF

ON

OFF

 

OUTPUT TYPE / PC CONFIG (SW1) 

Table 11

OUTPUT

SW1-4

SW1-3

SW1-2

SW1-1

0 – 20 mA

OFF

ON

OFF

OFF

-2.5 – +2.5 V

ON

OFF

OFF

ON

-10 – +10 V

ON

OFF

ON

OFF

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) DIP SW setting:  Check that the switches are set to ap-

propriate positions.

3) Power input voltage:  Check voltage across the terminal 

10 – 12 (AC) or 11 – 12 (DC) with a multimeter.

4) Input:  Check that the input signal is within 0 – 100% of 

full-scale.

  If the thermocouple, RTD, potentiometer, resistance or 

their extension wires are broken, the output goes over 

100% (below 0% with downscale protection) due to burn-

out function.  Confirm the status indicator LED pattern 

and check leadwires in such a case.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

I/O RANGING & FINE ADJUSTMENTS

After the DIP SW setting is complete, set up the precise 
input and output range using the front control buttons.  Be 
sure that the front control button function is enabled with 
the DIP switch setting.
The front LEDs’ colors and blinking patterns help you to 
easily identify the transmitter’s status and confirm the set-
up actions in each step of Calibration Modes.  Please read 
the following explanations referring to “Calibration Flow 
Chart”.

 

PREPARATION (e.g. M3LU-R4/A, DC powered type)

1) Mount the DIP-SW-configured M3LU on to a DIN rail.
2) Connect the M3LU to a simulator and a multimeter and 

to a DC power source as shown below.

3) Turn the power supply on and wait for 10 minutes.

3

5

7

8

11

12

M3LU

Multimeter

Simulator

+

Power Source

+ –

+

Example with V/mA input.
See Connection Diagram
for other input types.

Example with
DC power.

 

INPUT & OUTPUT RANGING

[Example] Setting both input and output to 1 – 5 V DC

1) Run Mode: Confirm that the green LED is blinking (mod-

el M3LU-x/A) or the green LED turns on (model M3LU-

x/B).

2) Input Ranging Mode: Hold down MODE button for longer 

than 5 seconds until the LD1 red LED is ON and the LD2 

red LED is blinking.

3) 0% Input Ranging: Apply the desired minimum input 

level (e.g. 1 V) from the simulator and hold down DOWN 

button until the LD1 blinks for approx. 2 sec. and then 

turns OFF.  When you release the button, the LD1 is re-

turned to ON.

  The blinking LD1 means that the value is stored in the 

memory.  If the LED does not change, the entered level 

may be inappropriate:  too small a span, or out of usable 

range (same for all steps).

4) 100% Input Ranging: Apply the desired maximum input 

level (e.g. 5 V) from the simulator and hold down UP but-

ton until the LD1 blinks for approx. 2 sec. and then turns 

OFF.  When you release the button, the LD1 is returned 

to ON.

5) Output Ranging Mode: Press MODE button and confirm 

that the LD3 red LED instead of LD2 is blinking.

6) 0% Output Ranging: Increase or decrease the simulated 

input until the meter shows the desired minimum output 

level (e.g. 1 V).  Hold down DOWN button until the LD1 

blinks for approx. 2 sec. and then turns OFF.  When you 

release the button, the LD1 is returned to ON.

7) 100% Output Ranging: Increase or decrease the simu-

lated input until the meter shows the desired maximum 

output level (e.g. 5 V).  Hold down UP button until the 

LD1 blinks for approx. 2 sec. and then turns OFF.  When 

you release the button, the LD1 is returned to ON.

8) Run Mode: When calibration is completed, press MODE 

button once and confirm that: the LD1 green LED is 

blinking in case of M3LU-x/A; and the LD1 green LED is 

ON in case of M3LU-x/B.

 

I/O RANGE LABEL

Blank I/O range labels are included in the product package.  
Write in the configured ranges and put the label on the side 
as shown below.

INPUT
OUTPUT

I/O Range Label (included in the product package)

Содержание M3LU

Страница 1: ...t must be mounted inside a panel Insert a noise filter for the power source connected to the unit TDK Lambda Noise Filter Model RSAN 2006 or equivalent is recommended The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance The actual installation env...

Страница 2: ... where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from the transmitter body for wiring insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALL...

Страница 3: ...the one connected with the CJC Sensor included in the package The CJC Sensor is secured to the terminal 6 Loosen only the terminal 4 5 and connect the T C extension wires Be aware that the AC power and DC power connect to different terminals AC POWERED TYPE B 1 3 2 4 5 6 CONFIGURATOR JACK 7 8 11 12 3 2 1 POT DC max min 2 wire RTD 3 wire RTD 4 wire RTD A A T C OUTPUT DC POWER B B A B A B VOLT mA mV...

Страница 4: ...0 75 8GY 0 5 to 0 75 mm2 AI 1 0 8RD 0 75 to 1 0 mm2 AI 1 5 8BK 1 0 to 1 5 mm2 Expose wire conductors by 8 mm 0 31 8 mm 8 mm 4 mm dia max 4 mm dia max Wire exposure Recommended ferruled wire EXTERNAL INTERNAL VIEWS 8 7 6 5 4 3 2 1 ON OFF ON OFF 4 3 2 1 Configuration DIP SW 10 11 12 7 8 9 4 5 6 1 2 3 Configurator Jack DOWN Button UP Button MODE Button LED3 LD3 LED2 LD2 LED1 LD1 FRONT VIEW SIDE VIEW ...

Страница 5: ... MODE SW3 8 Configuration mode can be Confirmed with the front LED DIP SW OFF PC ON FRONT CONTROL BUTTON LOCK SW2 Table 2 Table 2 setting is applicable to the firmware ID indicated below or higher versions marking on the product MASTER 2 01 SLAVE 1 05 LOCK SW2 6 PC Configuration is not dis abled when the front control button function is locked Unlock OFF Lock ON INPUT TYPE SW3 Table 3 INPUT SW3 7 ...

Страница 6: ...ator Power Source Example with V mA input See Connection Diagram for other input types Example with DC power INPUT OUTPUT RANGING Example Setting both input and output to 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LU x A or the green LED turns on model M3LU x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1 red LED is ON and the LD2 red ...

Страница 7: ... simulated 100 input signal Adjust simulated input until the output meter shows desired 0 output Adjust simulated input until the output meter shows desired 100 output LD1 LD1 ZERO SPAN ADJUSTMENTS After the transmitter is installed and operational fine zero and span tuning can be performed as explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the green LED is blin...

Страница 8: ...latinel II 20 20 20 20 270 to 1300 200 to 600 200 to 900 0 to 1395 130 to 1300 200 to 600 200 to 900 0 to 1395 0 30 0 20 0 25 0 25 36 36 36 36 454 to 2372 328 to 1112 328 to 1652 32 to 2543 202 to 2372 328 to 1112 328 to 1652 32 to 2543 0 54 0 36 0 45 0 45 RTD C F MIN SPAN MAXIMUM RANGE ACCURACY 1 MIN SPAN MAXIMUM RANGE ACCURACY 1 Pt 100 JIS 97 IEC Pt 200 Pt 300 20 20 20 200 to 850 200 to 850 200 ...

Страница 9: ... ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 11 Burnout in PC Configuration Mode Option A Burnout in DIP SW Configuration Mode PC Configuration RUN Mode Option A The transmitter is configured via PC and is in normal operating conditions DIP SW Configuration RUN Mode The transmitter...

Отзывы: