background image

M3LU

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-2652-A  Rev.2  P. 7 / 9

 

CALIBRATION FLOW CHART

POWER ON

Amber LED

Green LED

Control
Buttons

Red LED

OFF

ON

Blink

RUN MODE

LD2

LD3

A

G

RUN MODE

LD2

LD3

G

R

LD1

LD2

LD3

LD1

LD2

LD3

0% INPUT

CONFIGURED

100% INPUT

CONFIGURED

INPUT

RANGING

MODE

LD1

OUTPUT

RANGING

MODE

LD2

LD3

LD1

LD2

LD3

0% OUTPUT

CONFIGURED

100% OUTPUT

CONFIGURED

G

G

R

R

R

R

G

R

R

G

Fine Adjustments ?

I/O Ranging ?

HOLD DOWN  

MODE

 

 1 – 2 s

HOLD DOWN  

MODE

 

 > 5s

PRESS  

MODE

PRESS  

MODE

PRESS  

MODE

PRESS  

MODE

HOLD DOWN

DOWN

HOLD DOWN

UP

DOWN

UP

MODE

HOLD DOWN

DOWN

HOLD DOWN

UP

When you set 0% or 100% input/output ranges, 
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off, 
which indicates the setup is complete.
If the LED does not change, the entered level may
be inappropriate: e.g. out of usable range, burnout 
(wire breakdown).

*

For the model M3LU-x/A, the green LED is blinking.  

  For the model M3LU-x/B, the green LED turns on.

FINE ZERO

ADJUSTMENT MODE

UP

  or  

DOWN

FINE SPAN

ADJUSTMENT MODE

UP

  or  

DOWN

Apply simulated 0% input signal.

Apply simulated 100% input signal.

Adjust simulated input until the output meter 
shows desired 0% output.

Adjust simulated input until the output meter 
shows desired 100% output.

LD1

*

LD1

*

 

ZERO & SPAN ADJUSTMENTS

After the transmitter is installed and operational, fine zero and span tuning can be performed as explained below.
Both zero and span are adjustable within ±15%.

1) Run Mode: Confirm that the green LED is blinking 

(model M3LU-x/A) or the green LED turns on (model 

M3LU-x/B).

2) Fine Zero Adjustment Mode: Hold down MODE button 

for 1 or 2 seconds until the LD1 red LED is ON and the 

LD2 green LED is blinking.

  Use UP (increase) and DOWN (decrease) buttons to 

adjust the output to 0%.

3) Fine Span Adjustment Mode: Press MODE button and 

confirm that the LD3 green LED instead of LD2 is 

blinking.

  Use UP (increase) and DOWN (decrease) buttons to 

adjust the output to 100%.

4) Run Mode: When fine adjustment is completed, press 

MODE button once and confirm that: the LD1 green LED 

is blinking in case of M3LU-x/A; and the LD1 green LED 

is ON in case of M3LU-x/B.

Note 1:  Calibration steps can be skipped when not needed by 

repeating pushing MODE buttons.

Note 2:  There is no stated order of setting 0% and 100% levels 

or no limitation of entering values for multiple times 
within one step of Calibration Mode.  Signal level is 
stored each time the respective UP or DOWN button is 
pressed.

Содержание M3LU

Страница 1: ...t must be mounted inside a panel Insert a noise filter for the power source connected to the unit TDK Lambda Noise Filter Model RSAN 2006 or equivalent is recommended The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance The actual installation env...

Страница 2: ... where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from the transmitter body for wiring insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALL...

Страница 3: ...the one connected with the CJC Sensor included in the package The CJC Sensor is secured to the terminal 6 Loosen only the terminal 4 5 and connect the T C extension wires Be aware that the AC power and DC power connect to different terminals AC POWERED TYPE B 1 3 2 4 5 6 CONFIGURATOR JACK 7 8 11 12 3 2 1 POT DC max min 2 wire RTD 3 wire RTD 4 wire RTD A A T C OUTPUT DC POWER B B A B A B VOLT mA mV...

Страница 4: ...0 75 8GY 0 5 to 0 75 mm2 AI 1 0 8RD 0 75 to 1 0 mm2 AI 1 5 8BK 1 0 to 1 5 mm2 Expose wire conductors by 8 mm 0 31 8 mm 8 mm 4 mm dia max 4 mm dia max Wire exposure Recommended ferruled wire EXTERNAL INTERNAL VIEWS 8 7 6 5 4 3 2 1 ON OFF ON OFF 4 3 2 1 Configuration DIP SW 10 11 12 7 8 9 4 5 6 1 2 3 Configurator Jack DOWN Button UP Button MODE Button LED3 LD3 LED2 LD2 LED1 LD1 FRONT VIEW SIDE VIEW ...

Страница 5: ... MODE SW3 8 Configuration mode can be Confirmed with the front LED DIP SW OFF PC ON FRONT CONTROL BUTTON LOCK SW2 Table 2 Table 2 setting is applicable to the firmware ID indicated below or higher versions marking on the product MASTER 2 01 SLAVE 1 05 LOCK SW2 6 PC Configuration is not dis abled when the front control button function is locked Unlock OFF Lock ON INPUT TYPE SW3 Table 3 INPUT SW3 7 ...

Страница 6: ...ator Power Source Example with V mA input See Connection Diagram for other input types Example with DC power INPUT OUTPUT RANGING Example Setting both input and output to 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LU x A or the green LED turns on model M3LU x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1 red LED is ON and the LD2 red ...

Страница 7: ... simulated 100 input signal Adjust simulated input until the output meter shows desired 0 output Adjust simulated input until the output meter shows desired 100 output LD1 LD1 ZERO SPAN ADJUSTMENTS After the transmitter is installed and operational fine zero and span tuning can be performed as explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the green LED is blin...

Страница 8: ...latinel II 20 20 20 20 270 to 1300 200 to 600 200 to 900 0 to 1395 130 to 1300 200 to 600 200 to 900 0 to 1395 0 30 0 20 0 25 0 25 36 36 36 36 454 to 2372 328 to 1112 328 to 1652 32 to 2543 202 to 2372 328 to 1112 328 to 1652 32 to 2543 0 54 0 36 0 45 0 45 RTD C F MIN SPAN MAXIMUM RANGE ACCURACY 1 MIN SPAN MAXIMUM RANGE ACCURACY 1 Pt 100 JIS 97 IEC Pt 200 Pt 300 20 20 20 200 to 850 200 to 850 200 ...

Страница 9: ... ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 11 Burnout in PC Configuration Mode Option A Burnout in DIP SW Configuration Mode PC Configuration RUN Mode Option A The transmitter is configured via PC and is in normal operating conditions DIP SW Configuration RUN Mode The transmitter...

Отзывы: