LION Bus Coupler
▪
Error Handling
70
12
Error Handling
If any error will occur, the bus coupler will change into the failsafe status, which
cause following reactions:
▪ The TRDP communication is stopped.
▪ The L-Bus
2
communication is stopped, which forces all I/O modules in the
failsafe mode.
If monitoring functions recognize an error:
12.0.1
Consequences
12.0.2
- not applicable -
Check the configuration first.
In case of unexpected errors, please contact the service department.
Error
Operation
Status
Diagnosis
Telegram
Replacement
Values
Process
Variable
(Source
Telegram)
MS-/NS- LED
Invalid TDB
No cyclic
communication
TDB error
L-Bus²
will not
be started
No
communication
red/green
Timeout of one sink
telegram
Cyclic
communication
Timeout
Depending on
configuration
–
green/yellow
flashing
Timeout of all sink
telegrams
Cyclic
communication
Timeout
Depending on
configuration
–
green/red
not recognized
L-Bus² slave i
Cyclic
communication
comp. errors
Slot i
–
Values of the
slave set to 0
green/green
Consequences
Outputs
Will be switched off, internal and the digital/analog value is set
to 0 or hold on the last valid value and send it via the L-Bus
2
,
depending on the TDB.
Read chapter "Voltage Monitoring” on page 41.
Inputs
Will be switched off, internal and the digital/analog value is set
to 0 and is sent via the TRDP bus.
Содержание 803012
Страница 1: ...Operating Instructions LION Bus Coupler Ethernet SIL0 LION BC ETH LUE 803012 Version 01 03 19 2019 ...
Страница 63: ...LION Bus Coupler Operation 64 Module not recognized Unexpected module ...
Страница 64: ...LION Bus Coupler Operation 65 Wrong safety checksum ...
Страница 75: ... by Lütze Transportation GmbH Weinstadt Germany Technical changes reserved ...