LION Bus Coupler
▪
System Planning
24
4.5
System Architecture
Different system architectures can be realized with the LION product family.
Following points are important to realize a system:
▪ The SIL0/SIL2 bus coupler is the master of the LION system, the SIL0/SIL2
I/O modules are slaves.
▪ Max. 3 lines are possible.
▪ The maximum distance between two lines should be no longer than 10 m.
▪ The first component of every line must be a SIL0/SIL2 power supply. Other
SIL0/SIL2 power supplies can follow.
▪ The second component of the first line must be the SIL0/SIL2 bus coupler.
▪ If the system consist of different lines, the last component of the line is a SIL0
line coupler and in the following line the second component must be also a
SIL0 line coupler.
▪ It is possible to connect max. 32 SIL0/SIL2 I/O modules to the SIL0/SIL2 bus
coupler.
▪ It is not allowed to create a line which is longer than 2 m.
▪ SIL0 and SIL2 I/O modules can be combined in the system.
▪ A module is the smallest exchangeable unit in the system.
Different system architectures can be found below:
4.5.1
Smallest System
The smallest system contains:
1. one SIL0/SIL2 power supply,
2. one SIL0/SIL2 bus coupler and
3. one SIL0/SIL2 I/O module.
All components are in one line.
Fig. 12: System Architecture – Smallest System
Using the SIL0 bus coupler only SIL0 can be reached.
Содержание 803012
Страница 1: ...Operating Instructions LION Bus Coupler Ethernet SIL0 LION BC ETH LUE 803012 Version 01 03 19 2019 ...
Страница 63: ...LION Bus Coupler Operation 64 Module not recognized Unexpected module ...
Страница 64: ...LION Bus Coupler Operation 65 Wrong safety checksum ...
Страница 75: ... by Lütze Transportation GmbH Weinstadt Germany Technical changes reserved ...