User Manual CM-CAN1
7-5
7 Examples
DE
EN
7.1.3 Parameter set-
ting
Action
ID
Data
Comments
Enquire for
parameter
1103
68 01 05 XX XX
XX XX 00
Poll parameter to be displayed as
continuous actual value (parameter
360-DISP)
Reply from CDA 1323
68 01 00 96 01
00 00 00
Message: Parameter
360-DISP = 406 (406-REFF Current
reference frequency)
Send parameter 1103
68 01 02 0E 00
00 00 00
Set parameter
360-DISP to 14-MIST (actual torque)
Reply from CDA 1323
68 01 00 0E 00
00 00 00
Checkback from CDA after success-
ful data transfer
Table 5.16
Example of parameter setting