4 Setting the device parameters
489-CLBDR - CAN bus baud rate
By way of this parameter the baud rate of the CAN controller is set.
Attention: A change of device address or baud rate only takes effect
after the next reset (restart) of the inverter!
Before the reset save the settings in the device with parame-
ter 150-SAVE!
574-CAWDG - Bus watchdog time in ms
Value for watchdog to monitor the CAN bus. The watchdog time is adjust-
able in millisecond increments. The value 0 deactivates the watchdog.
Subject area
Value range
Factory set.
Unit
Data type
Memory type
_57OP
25 ... 500
500
kBaud
USIGN8
FLASH
CLBDR
*
Transmission speed
Comments
0
500 kBaud
Factory setting
1
250 kBaud
2
125 kBaud
3
75 kBaud
4
50 kBaud
5
25 kBaud
* - Transfer value for parameter setting
Table 4.7
Baud rate
Subject area
Value range
Factory set.
Unit
Data type
Memory type
_57OP
0 ... 255
0
ms
USIGN8
FLASH