User Manual CM-CAN1
2-5
2 Mounting and connection
DE
EN
2.3
Electrical
installation
Figure 2.4 System connection. (1) Bus termination plug
Step
Action
Comment
1
Connect the module to the field bus. Use
a cable conforming to the specification.
Use a bus termination plug
(120
Ω
) on the last module -
2
Wire the controller enable on the
CDA3000.
3
Wire up the supply voltage for the mod-
ule.
19 ...29 VDC see Table 3.2
4
Switch on the drive unit.
Electrical installation is finished; for the further procedure see section 3
“Commissioning and configuration”.
Characteristics
CM-CAN1
Voltage supply
19 ... 29 V, supply
optionally
via X10, X11 or X12
Voltage ripple
max. 3 Vss
Current consumption
max. 80 mA per station
Cable type
9-wire, surge impedance 120
Ω
Table 3.2
Specification, CAN bus connection
L-
L1
L+
N
24 VDC
C A N - B u s
,
,
12
12
,
,
Slave 2
M
3
~
Slave 1
M
3
~
,
,,
11
12
13
14
15
16
17
18
19
20
12
34
5
6
7
89
10
11
12
13
14
15
16
17
18
19
20
12
3
4
56
7
8
9
10
SPS/PLC
,
12
,
,
Slave n
M
3
~
(1)
1
120 E
2
7