6-6
User Manual CM-CAN1
6 Fault rectification
6.3
Parameteriz-
able warnings
on the CAN
Bit coded warning messages
Note:
Several warning messages may be present at any one
time.
Priority based on
CAL
Display
Base ID
Data byte
0
Data byte
1-2
2
Warning
active
441*
Error no.
Always FF
Warning bit
coded 1 Word
* Signaled if the status of the bit coded warning word changes.
Table 5.12
Warnings
Bit in data byte
1-2
Hex value
Function
0
0001H
Warning message when DC-link voltage has fallen below
value in parameter 503-WLUV
1
0002H
Warning message when DC-link voltage has exceeded
value in parameter 504-WLOV
2
0004H
Warning message when I
2
*t integrator of device is active
3
0008H
Warning message when motor temperature has
exceeded value in parameter 502-WLTM
4
0010H
Warning message when heat sink temperature has
exceeded value in parameter 500-WLTI
5
0020H
Warning message when interior temperature has
exceeded value in parameter 501-WLTD
6
0040H
Warning message when apparent current has exceeded
value in parameter 506-WLIS
7
0080H
Warning message when output frequency has exceeded
value in parameter 505-WLF
8
0100H
Warning message from slave when reference value from
master is faulty in Master/Slave operation
9
0200H
Warning message when Ixt integrator of motor is active
10 - 15
Reserved
Table 5.13
Warning messages (corresponds to Warnings status word,
parameter 120-WRN in subject area _50WA)
Содержание CM-CAN1
Страница 8: ...User Manual CM CAN1...
Страница 28: ...3 6 User Manual CM CAN1 3 Commissioning and configuration...
Страница 50: ...4 22 User Manual CM CAN1 4 Setting the device parameters...
Страница 72: ...6 8 User Manual CM CAN1 6 Fault rectification...
Страница 78: ...7 6 User Manual CM CAN1 7 Examples...
Страница 83: ......