4 Setting the device parameters
DE
EN
4.1.2 Mapping data
types
All data types are represented appropriate to their preceding sign as
32-bit variables in Intel format.
FLOAT32
see IEEE
32-bit floating point number in IEEE format
ERR_STRUC
–
Error number (1 byte), error location (1 byte),
error time (2 bytes)
STRING
–
ASCII characters, max. 100 bytes in bus
operation incl. zero terminator
Table 4.1
Data types
Bytes
3
4
5
6
USIGN8/INT8 *
USIGN16/INT16 *
USIGN32/INT32
Low Word Low
Byte
Low Word High
Byte
High Word Low
Byte
High Word High
Byte
INT32Q16
Post-point L
Post-point H
Pre-point L
Pre-point H
FIXPOINT16 *
See examples, Table 4.3
FLOAT32
IEEE format
ERR_STRUC
Error no.
Error location
TOP L
TOP H
STRING
See examples, Table 4.3
* Filled out appropriate to preceding sign (00H or FFH)
TOP = Time of OPeration in full hours
Table 4.2
Arrangement of data types in the data field
L
Low Byte
H
High Byte