User Manual CM-CAN1
3-3
3 Commissioning and configuration
DE
EN
3
152-ASTER: Proposal: BUS 1-3 preselects the setting for CLSEL and RSSL1
For more detailed information on optimization of the software functions
and control circuits refer to the device application manual.
Step
Action
Comment
6
Start initial commissioning as specified in
the Operation Manual.
Acquisition of motor-specific
data and automatic calculation
of the parameters of the various
control circuits
7
Configure the drive unit using the
Application Manual.
(Inputs/outputs, software
functions, ...)
8
Test the control quality
and optimize the
controller settings as necessary using the
Operation Manual.
9
Set the CAN-specific parameters (refer to
section 4.2).
For an initial test of CAN
communication the following
settings are required as a
minimum: See Table 3.1.
10
Test the drive on the higher-order
controller
11
Finally, save the setting with parameter
150 -SAVE = START (1); See section
3.5.1.
Parameter
Value
Comments
489-CLBDR
Baud rate
Baud rate setting, factory setting = 500kB
571-CLADR
Address
Device address, factory setting = 0
260-CLSEL
OPTN2 (5)
Assign control location to CAN
LUST
280-RSSL1
FOPT2
Apply reference value from CAN
LUST
150-SAVE
START (1)
Finally, save settings in device
Table 3.1
Minimum parameters to be set
Содержание CM-CAN1
Страница 8: ...User Manual CM CAN1...
Страница 28: ...3 6 User Manual CM CAN1 3 Commissioning and configuration...
Страница 50: ...4 22 User Manual CM CAN1 4 Setting the device parameters...
Страница 72: ...6 8 User Manual CM CAN1 6 Fault rectification...
Страница 78: ...7 6 User Manual CM CAN1 7 Examples...
Страница 83: ......