Example: Initial commissioning
1.
Selection of an application data set to handle the movement
task
1.1
Call up "Initial commissioning" subject area
1.2
Select parameter RUNMD and set to “1”
This activates the presetting for traction and lifting drives
1_DRV = Traction and lifting drive
2_ROT = Rotational drive
3_BUS = Field bus operation
4_M-S
= Master-/Slave operation
2.
Adaptation of the control terminal function to the application
2.1
Call up parameter ASTER and select setting DRV_3
The control terminal is assigned the quick jog/slow jog driving pro-
file and limit switch evaluation functions.
6
Select control mode
•
Voltage Frequency Control
•
Sensorless Flux Control
•
Field-Oriented Regulation
7
Save all settings in a user data set
•
Initial commissioning com-
plete
*)
For more information on application data sets and assistance parameters refer to
section 4.2.
Motor:
Asynchronous motor 1.5 kW
Application:
Linear drive with limit switches,
moment of inertia of application 0.003 kgm².
Positioning is to be dynamic with a quick jog/slow
jog profile.
Step
Function
Explanation
Table 4.2
Sequence of initial commissioning
Содержание CDA3000
Страница 62: ...Engineering Guide CDA3000 2 29 2 Drive definition DE EN 1 2 3 4 5 6 7 A Notes ...
Страница 315: ...A 24 Engineering Guide CDA3000 Appendix A Formula bank Movement by rack Movement by cable reel Movement by spindle ...
Страница 317: ...A 26 Engineering Guide CDA3000 Appendix A Formula bank Indexing table with eccentric loads ...
Страница 336: ...Engineering Guide CDA3000 A 45 DE EN FR 1 2 3 4 5 6 A Appendix B Practical working aids for the project engineer ...