Engineering Guide CDA3000
6-15
6 Selection of supplementary components
DE
EN
1
2
3
4
5
6
7
A
6.4.2 Permissible
motor cable
length with
internal RFI filter
[A]
[B]
[C]
[D]
[E]
[F]
4 kHz power stage clock
frequency
8 kHz 8 kHz power stage contact
frequency
16 kHz power stage contact
frequency
Inverter
module
Rec. 4-pole
standard
motor
[kW]
With integral
mains filter
With
[A]
and
line choke U
K
=4%
With integral
mains filter
With
[C]
and
line choke U
K
=4%
With integral
mains filter
With
[E]
and line
choke U
K
=4%
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
CDA32.003
0.375 kW
25
10
25
10
25
10
25
10
25
-
25
-
CDA32.004
0.75 kW
25
10
25
10
25
10
25
10
25
-
25
-
CDA32.006
1.1 kW
15
10
15
10
25
15
25
15
25
-
25
-
CDA32.008
1.5 kW
15
15
15
15
25
15
25
15
25
-
25
-
CDA34.003
0.75 kW
15
15
25
15
25
10
25
15
25
-
25
-
CDA34.004
1.1 kW
15
15
25
15
25
10
25
15
25
-
25
-
CDA34.005
1.5 kW
15
15
25
15
25
10
25
15
25
-
25
-
CDA34.006
2.2 kW
15
15
25
15
25
10
25
10
25
-
25
-
CDA34.008
3.0 kW
25
10
25
15
25
-
25
10
25
-
25
-
CDA34.010
4.0 kW
25
10
25
15
25
-
25
10
25
-
25
-
CDA34.014
5.5 kW
25
10
25
15
25
10
25
25
15
-
25
15
CDA34.017
7.5 kW
25
10
25
15
25
10
25
25
15
-
25
15
1) Maximum permissible motor cable length at which the standard is maintained
Table 6.14
Permissible motor cable length with integral mains filter
dependent on standard EN 55011 A/B
Содержание CDA3000
Страница 62: ...Engineering Guide CDA3000 2 29 2 Drive definition DE EN 1 2 3 4 5 6 7 A Notes ...
Страница 315: ...A 24 Engineering Guide CDA3000 Appendix A Formula bank Movement by rack Movement by cable reel Movement by spindle ...
Страница 317: ...A 26 Engineering Guide CDA3000 Appendix A Formula bank Indexing table with eccentric loads ...
Страница 336: ...Engineering Guide CDA3000 A 45 DE EN FR 1 2 3 4 5 6 A Appendix B Practical working aids for the project engineer ...