6-6
Engineering Guide CDA3000
6 Selection of supplementary components
6.1.3 Technical data
of line chokes
LR3x.xxx
If several inverter modules are connected
to one line choke, it must be ensured that
the sum of the inverter rated currents does
not exceed the rated current of the line
choke.
Ambient conditions
LR 32. xxx
LR 34. xxx
Rated voltage
1 x 230 V, -20 % +15 %, 50/60 Hz
1)
3 x 460 V, -25 % +10 %, 50/60 Hz
1)
Overload factor
1.8 x I
N
for 40 s
1.8 x I
N
for 40 s up to rated current 32 A
1.5 x I
N
for 60 s above rated current 45 A
Ambient temperature
typically -25° C to +45° C, with power reduction to 60° C
Mounting height
1000 m, with power reduction to 4000 m
Relative air humidity
15 ... 95 %, condensation not permitted
Storage temperature
-25° C to +70° C
Protection
IP00, terminals VBG4
Short-circuit voltage
UK 4 % at 230 V = 9.2 V
UK 4 % at 400 V = 9.24 V
Permissible contamination
P2 to EN 61558-1
P2 to EN 61558-1
Thermal configuration
I
eff
< I
N
Material
Only UL-listed materials are used
Table 6.4
General technical data of line chokes LR3x.xxx
Σ
I
Invert
er
I
N
Linechoke
≤
Содержание CDA3000
Страница 62: ...Engineering Guide CDA3000 2 29 2 Drive definition DE EN 1 2 3 4 5 6 7 A Notes ...
Страница 315: ...A 24 Engineering Guide CDA3000 Appendix A Formula bank Movement by rack Movement by cable reel Movement by spindle ...
Страница 317: ...A 26 Engineering Guide CDA3000 Appendix A Formula bank Indexing table with eccentric loads ...
Страница 336: ...Engineering Guide CDA3000 A 45 DE EN FR 1 2 3 4 5 6 A Appendix B Practical working aids for the project engineer ...