3-6
Engineering Guide CDA3000
3 Selection of inverter module
3.1.2 Ambient
conditions
EN 50081-1
•
Residential and business
•
Motor cable length - See
section 6.4
Protection against emission of electri-
cal, magnetic and electromagnetic
interference and against conducted
interference
EN 50081-2
•
Industrial
•
Motor cable length - See
section 6.4.2
Protection against emission of electri-
cal, magnetic and electromagnetic
interference and against line-borne
interference
EN 55011
•
Industrial
Class A
Protection against line-borne interfer-
ence
•
Residential and business
Class B
•
Motor cable length - See
section 6.4
Standard
Test
Comments
Table 3.4
Explanation of the “Acceptance tests and standards” table
Feature
Characteristic data
Tempera-
ture range
in operation
-10 ... 45 °C with derating to 55 °C (BG1 ... BG5)
0 ... 40 °C (BG6 ... BG8)
in storage
-25 ... +55 °C
in transit
-25 ... +70 °C
Relative air humidity
15 ... 85 %, condensation not permitted
Mechanical
strength to
IEC 68-2-6
in stationary
operation
Vibration: 0.075 mm in frequency range 10 ... 58 Hz
Shock: 9.8 m/s
2
in frequency range >58 ... 500 Hz
in transit
Vibration: 3.5 mm in frequency range 5 ... 9 Hz
Shock: 9.8 m/s
2
in frequency range >9 ... 500 Hz
Protection
Device menu
IP20 (NEMA 1)
Cooling
method
Cold plate IP20
Push-through heat sink IP54 (3...15kW)
Push-through heat sink IP20 (22...37kW)
Touch protection
VBG 4
Power reduction
See section 3.2.x
Table 3.5
Ambient conditions
Содержание CDA3000
Страница 62: ...Engineering Guide CDA3000 2 29 2 Drive definition DE EN 1 2 3 4 5 6 7 A Notes ...
Страница 315: ...A 24 Engineering Guide CDA3000 Appendix A Formula bank Movement by rack Movement by cable reel Movement by spindle ...
Страница 317: ...A 26 Engineering Guide CDA3000 Appendix A Formula bank Indexing table with eccentric loads ...
Страница 336: ...Engineering Guide CDA3000 A 45 DE EN FR 1 2 3 4 5 6 A Appendix B Practical working aids for the project engineer ...