P30P-09A 64 User's manual
the transducer;
4091
BaudRate
w/r
0...2
0
Baud rate of the Ethernet interface:
Value
Description
0
Automatic selection of the baud rate
1
10 Mb/s
2
100 Mb/s
4092
p.comFTP
w/r
20...65535
21
FTP server commands port number
4093
port FTP
w/r
20...65535 1025 FTP server data port number
4094
no.c.TCP
w/r
1...4
4
The maximum simultaneous connections to Modbus
TCP/IP service
4095
TimeMbus
w/r
10...600
60
Port closing time of Modbus TCP/IP service, in
seconds
4096
AddrmTCP
w/r
0...255
1
Device address for Modbus TCP/IP protocol
4097
PortMbus
w/r
0...65535
502
Modbus TCP port number
4098
portHTTP
w/r
80...65535
80
Web server port number
4099
ReInitEt
w/r
0...1
0
Saving the new parameters and initiate Ethernet
interface
Value
Description
0
No change
1
Saving the new parameters and initiate
Ethernet interface
4100
ParamAn1
w/r
0..16
7
Input value controlling the analog output 1
Value
Description
0
Register values 7500 - voltage
1
Register values 7501 – current
2
Register values 7502 – active power
3
Register values 7503 – reactive power
..
..
7
Frequency
...
...
14
Register values 7514 - temperature
15
Second value displayed
16
Clock
4101
OverSer1
w/r
0...1
0
Analog output 1overrun support
Value
Description
0
Off
1
On
4102
OvOutLo1
w/r
0...24000
0
Output 1 lower overrun value x1000
4103
OvOutHi1
w/r
0...24000
20000
Output 1 upper overrun value x1000