P30P-09A 27 User's manual
AddrmTCP
Device address for Modbus TCP/IP protocol
0 255
…
PortMbus
Modbus TCP port number
0 65535
…
TimeMbus
Port closing time of Modbus TCP/IP service,
in seconds
10 600
…
no.c.TCP
The maximum simultaneous connections to
Modbus TCP/IP service
1 4
…
p.comFTP
FTP server commands port number
20...65535
port FTP
FTP server data port number
20...65535
portHTTP
Web server port number
80...65535
BaudRate
Baud rate
Auto
automatic
10 Mb/s
10 Mbit/s
100 Mb/s
100 Mbit/s
EthStdPa
Setting the new parameters of Ethernet
interface
Yes
Restoring the default parameters of
Ethernet interface
No
no change
ReInitEt
Saving the new parameters of the Ethernet
interface
Yes
Saving the new parameters and initiate
Ethernet interface
No
no change
Table 10
Settings
Support
Parameter
symbol
Description
Range of changes
Fabr.Par
Entering default setting. Setting "yes" value
resets transducer parameters to their default
values. Values of default parameters are
presented in Table 15.
No
do nothing
Yes
sets default factory values.
Security
Entering new password. Entering 0 value
turns password protection off.
-99999...99999
Time
Setting the current time. Entering invalid
time value cancels time setting. Entered
value will not be used.
00:00...23:59
Date
Date setting - month+day. Entering invalid
date value cancels date setting. Entered
value will not be used.
01-01-10...31-12-99
AutoTime
Automatic DST and inversely
No
no automatic daylight saving time
change
Yes
with automatic daylight saving time
change
DispTest
LCD display and LED indicators test
No
do nothing
Yes
starts the test
Language
Menu language selection
Polish
selection of Polish language
English
selection of English language
SaveFile
No
do nothing
Yes
Forced transducer configuration file
saving to the external SD/SDHC card
or file system internal memory