P30P-09A 32 User's manual
If the transducer is equipped with additional analog output (no. 2), it should be configured in
the same way as main output, using the transducer → parameter menu:
ParamAn2
…
OvrOutH2
or
with registers (according to their description in Tab. 35).
Caution!
If the transducer is not equipped in additional analog outputs, then relevant parameters are not available.
If the analog output has the threshold handling turned on, then configuration parameters for threshold
handling are not available in the menu.
5.5.3 Alarm and power outputs
P30P transducer can be equipped with 2 normally open alarm contacts or 1 output with
normally open contact and 1 24 VDC power output. (depending on version) Each alarm (24 VDC power
output should be treated like one) can operate in one of six available modes. The Fig. 12 presents alarm
operating in the following modes: n-on, n-off, on, off. Other two modes: h-on and h-off stand for always
on and always off, respectively. These modes are used for manual simulation of the alarm state.
In case of the transducer version fitted with 24 VDC power output, second alarm should set as
h-on, the auxiliary power output will be always on.
Fig. 12 Alarm types: a) n-on; b) n-off; c) on; d) off.
AL_L - Alarm lower limit
AL_H – Alarm upper limit
Caution:
In case of alarm type
n-on
,
n-off
,
on
,
off
entering the AL_L > AL_H value will disable the
alarm.