P30P-09A 37 User's manual
5.5.5.1 Saving transducer configuration file
Writing of the current configuration file is possible after selecting a
Service SaveFile
→
Yes
→
option from the menu or after entering value “1” into register 4078. Configuration text file will be
saved in the
P30P
folder, filename:
P30P_PAR.CON
(point 5.8.4, Fig. 19). Subsequent configuration file
write command will overwrite previously created file.
5.5.5.2 Reading transducer configuration file
Loading the transducer configuration from the file allows for quick configuration of the
transducer equipped with the external SD/SDHC card or file system internal memory. Configuration file
should be located in the
P30P
folder and be named
P30P_PAR.CON.
File can be generated by properly
configured P30P transducer or by the eCon software used to configure P30P transducers (ModBus
RS-485 or TCP/IP). For P30P transducers in P30P-XX2XXXXXX version, file can be transferred
between devices via FTP. For P30P transducers in P30P-XX1XXXXXX version, single file on a memory
card can be used to configure several transducers equipped with SD card slot.
To force parameter update from the file, power the transducer on while holding the following
button:
. If the file contains correct data and the configuration is accepted, the display will show
following message:
Fig. 15 Message after successful loading of the configuration file.
If the parameter update was forced but no file was present or the file contains invalid data (at least one
invalid parameter), the current configuration is not overwritten and the following message appears on the
display:
Fig. 16 Message after unsuccessful loading of the configuration file
5.6. Default settings
Table 17
shows the standard settings of the P30D transducer. These settings can be reverted
via the following option in the transducer menu:
Settings Service Fabr.Par
→
→
Yes
or
via the RS-485 interface after entering value “1” into register 4055.