P30P-09A 12 User's manual
RS-485 interface, the link parameters: baud rate 9600 bit/s, 8N2 mode.
- increase value button
●
change of the displayed value,
●
navigation within selected level,
●
change of the selected parameter value – value increase,
- digit change button
●
change of the displayed value
●
moving to the parameter group level,
●
navigation within selected level
●
selected parameter value change – moving to subsequent number
●
turning the transducer on and holding down the button - entering into software update mode via
RS-485 interface, the link parameters: baud rate 115200 bit/s, 8N2 mode.
- cancel button
●
enters the transducer parameter display mode (hold the button for at least 3 seconds),
●
quits the transducer parameter display menu
●
change of content displayed on the bottom line of the display
●
cancels the parameter change
●
forced exit from the programming mode (hold the button for at least 3 seconds),
●
turns the transducer with the button pressed – forces loading transducer configuration from the
P30P_PAR.CON file saved to the external SD/SDHC card or internal file system memory
(depends on the version).
5.3.2. Functions of button combinations
- holding down for approx. 3 second
●
deletes alarm signalization; this operation works only with support function turned on;
- holding down for approx. 1 second
●
displays maximum of the currently displayed value
- holding down for approx. 1 second
●
displays minimum of the currently displayed value