P30P-09A 20 User's manual
IDM
Current averaged
cos
Cosine of the angle between U and I
THD U
Harmonic distortion factor of voltage
THD I
Harmonic distortion factor of current
Temper.
temperature
2nd Val
second value displayed
Time
time
Type A1
Type A2
Alarm type. Fig. 12 shows the
rendering of the alarm types.
n-on
normal (change from 0 to 1).
n-off
normal (change from 1 to 0).
on
on
off
off
h on
_
manual off; alarm output is permanently
switched on until change of the alarm
type.
h off
_
manual off; alarm output is permanently
switched on until change of the alarm
type.
OverLoA1
OverLoA2
Alarm lower limit
-99999G...99999G
OverHiA1
OverHiA2
Alarm upper limit
-99999G...99999G
DlyOnA1
DlyOnA2
Alarm activation delay (s)
0...900
DlyOffA1
DlyOffA2
Alarm deactivation delay (s)
0...900
OnLockA1
OnLockA2
Alarm re-activation delay (s)
0...900
SgKeepA1
SgKeepA2
Alarm signalization latch after the
alarm is off (alarm memory)
Off
no alarm signalization latch
On
alarm signal support by the pulsating A1
and A2 LEDs after the alarm sound ends
Table 4
Settings
Display
Parameter
symbol
Description
Range of changes
Bcklight
Time of a display panel illumination
On
- permanently switched on
Off
- permanently switched off
1
- switched on for X seconds
2
…
60
Bckl.Int
Intensity of LCD display panel illumination
10%
- LCD display panel illumination, 10% of max.
illumination
20%
- LCD display panel illumination, 20% of max.
illumination
…
100%
- LCD display panel illumination, 100% of
max. illumination
Disp.Reg
Register number displayed on the bottom
line of the display
0...65535