background image

6646 Complex Drive | Baton Rouge, LA 70809 | Phone: 225-456-2495 | Toll Free: 1-800-223-8469 | [email protected] | www.jogler.com

Page 1

JLT-6000 .IOMM.REV 001 (06.2007)                                   WWW.JOGLER.COM 

          PAGE 1  

__________________________________________________________________________________

Installation 

and 

Operating 

Manual             

    

 

JLT-6000 

__________________________________________________________________________________

Magnetostrictive Level Transmitters 

Series JLT-6000 

June, 2007 

Jogler, Incorporated 

9715 Derrington Road 

Houston, Texas USA 

77064

Telephone:  281.469.6969 

Toll Free:     800.223.8469 

Telefax:    281.469.0422 

www.jogler.com

      

 

 

 

 

      

       

                          

6646 Complex Drive

Baton Rouge, LA 70809

Phone: 225-456-2495

Toll Free: 1-800-223-8469

[email protected]

www.jogler.com

Summary of Contents for JLT-6000 series

Page 1: ...____ Installation and Operating Manual JLT 6000 __________________________________________________________________________________ Magnetostrictive Level Transmitters Series JLT 6000 June 2007 Jogler Incorporated 9715 Derrington Road Houston Texas USA 77064 Telephone 281 469 6969 Toll Free 800 223 8469 Telefax 281 469 0422 www jogler com 6646 Complex Drive Baton Rouge LA 70809 Phone 225 456 2495 T...

Page 2: ... 4 2 1 0 Introduction 2 2 0 Unpacking 2 3 0 Storage 2 4 0 Electronic Discharge 2 5 0 Equipment Tools 2 6 0 Temperature Ratings 2 7 0 Pressure Ratings 2 8 0 Voltage 3 0 0 Mounting Page 6 3 1 0 Introduction 3 2 0 MGT Magnetic Level Gage 3 3 0 ILT Direct Tank Insertion 3 4 0 LGT Level Gage Insertion 4 0 0 Wiring Page 7 4 1 0 Initial Connection 4 2 0 Reconnection 5 0 0 Transmitter Configuration Page 8...

Page 3: ...osed to external process conditions Remote mounted transmitter head locations are available The LGT 6000 series transmitter is designed for installation directly into a liquid level sight glass The patented LGT design provides 100 confirmation between the liquid level in the gage and the float position of the transmitter relative to the fluid level established in the sight glass Top bottom or remo...

Page 4: ...the shipping container until all components are accounted and inspected for 2 3 0 Storage If the transmitter requires storage for prolonged periods care must be given to ensure product protection from physical and ambient conditions Seal the entire device completely from condensation and store it with the shipping materials provided Do not leave any auxiliary conduit connection open Recommended st...

Page 5: ...e maximum process temperature rating of the JLT series transmitter is 40 F to 235 F and applies to the waveguide probe 2 7 0 Pressure Ratings The maximum process pressure rating of the JLT series transmitter waveguide probe is 300 PSIG This rating applies to LGT 6000 series which is a direct insertion model for level gage applications only The waveguide probe in the ILT 6000 series transmitter is ...

Page 6: ...t position which should be spaced evenly apart throughout the waveguide Secure the L brackets by tightening each pipe clamp accordingly after the transmitter head is secured 3 3 0 ILT Direct Tank Insertion Waveguide with Thermowell The assembly includes a welded flanged thermo well and float that is separate from the transmitter head and waveguide Verify if the flanged thermo well and float assemb...

Page 7: ...e transmitter puck out vertically and carefully There are three guide pins located on the bottom of the transmitter puck housing These pins realign the puck perfectly into the termination board upon reinstallation Photograph Nos 3 and 4 Wiring to the terminal block is as follows Terminal Block POS Positive 24 VDC Red Wire Terminal Block NEG Negative Black Wire Ground Screw 8 32 NC Inside Enclosure...

Page 8: ... key selects the set mode when on a menu screen where it is available The Select key also accepts a value and moves to the next step when in the set mode The scroll or set mode is indicated by the lack or presence of the set mode symbol in the upper right hand corner of the screen Screen scrolling is in ascending order of screen number when the down arrow is depressed and descending order when the...

Page 9: ...level value 5 3 5 Screen 5 Dft Display Category User Setting Input Scroll Level Level Loop scroll selectable Description Selects the default screen display as either Scroll Level Level or Loop Notes None 5 3 6 Screen 6 Quick Cal Category User Setting Input Select 4 mA and 20 mA points based on float position Description Allows the setting of the 0 and 100 points based on the current float position...

Page 10: ...10 20 Ma Set Category User Setting Input Position of the 20 milliamp 100 point in inches or cm 5 3 11 Screen 11 Offset Category User Setting Input PV measurement offset in inches or cm Description A positive or negative adjustment to the PV zero reference mark 5 3 12 Screen 12 Damping Category User Setting Input Value of the damping time constant in seconds Description Sets value of the damping ti...

Page 11: ... Trims the 20 mA output of the 4 20 mA loop Notes Performs a trim of the DAC 5 3 18 Screen 18 Mnt Pos Category User Setting Input Tom Bottom scroll selectable Description Defines type of mounting as either top or bottom mounted 5 3 19 Screen 19 DeadZone Category Factory Setting Input Distance in inches or cm Description This is an ignored region dead zone measured from the sensing element Any sign...

Page 12: ...level signal 5 3 24 Screen 24 Puls Amp Category Factory Setting Input Integer from 0 255 representing the amplitude of the sensor wire current pulse Description Gain setting for sensor wire current pulse 5 3 25 Screen 25 DeviceID Category Factory Setting Input Yes No scroll selectable Description If Yes is selected the Device ID will be set equal to the Final Assembly Serial Number and stored in n...

Page 13: ... 0 0 Maintenance 6 1 0 Standard The JLT 6000 series transmitters are designed for long life and maintenance free performance Periodic inspection by the owner operator should be performed at regular scheduled intervals If any component of the JLT series transmitter reveals signs of extensive corrosion or wear please contact the factory immediately for recommended corrective action Programmable chan...

Page 14: ... under the standard warranty Jogler will replace or repair the device at no cost to the owner Jogler is not liable for warranty claims on any level control that has been misapplied mishandled or installed improperly based on the parameters outlined in this manual This also applies to products damaged by freight without claims filed in a timely manner 7 2 0 Quality Control Jogler s quality control ...

Page 15: ...sable Region 1 00 inch at end of probe Dead Zone 0 00 inch user specify Humidity 0 00 99 0 non condensing 7 4 2 Electrical Input 12 30 VDC 24 VDC Nominal Output 4 20 mA Resistance 600 Ohms max 24 VDC Power Consumption 0 66 Watt 30 VDC x 0 022 ohms 0 66 W Error Signal 3 60 or 22 mA Interface 3 button keypad HART or PACT software Display 2 line 8 character LCD Values Inches or centimeters percent of...

Page 16: ...___ Installation and Operating Manual JLT 6000 __________________________________________________________________________________ 7 5 0 Industry Approvals Agency Model Protection Area Classification FM ILT 6000 Intrinsically Safe Class I Division 1 CSA LGT 6000 Groups A B C D MGT 6000 Class II Division 1 Groups E F G Class III Nema Type 4X ILT 6000 Explosion Proof Class I Division 1 LGT 6000 Group...

Reviews: