UNITOUR Power System
User Manual
Page 40
3.18
Configure sACN
Streaming ACN (sACN) is an informal name for the E1.31 streaming protocol to transport
multiple DMX universes over a single Ethernet cable/network.
To enable the sACN input, from the f
rom the “Home Menu” tap
LOG IN
,
ADVANCED
,
CONFIGURE sACN
.
Configure sACN
Tap the up
or down
buttons to select the universe to which the UNITOUR rack will
respond then tap
SAVE
.
If sACN is enabled, any matching universes on the network will appear in the bottom right
window. The information includes the universe number, priority, source IP address, whether
the sACN data includes DMX, and ‘other’ information.
sACN uses a priority system. The priority level is set by the sACN transmitting device. If
UNITOUR receives more than one sACN signal on the selected universe it will only respond
to the signal with the highest priority setting.
Note: To use sACN, UNITOUR must have a valid IP address and NetMask set in order to work
correctly. See section 3.21.1
3.19
Set Power Limits
UNITOUR monitors the input voltages of all 3 input phases and the neutral. You can set
voltage limits that will protect the connected loads by switching off the relevant outputs and
activating an alarm if the input voltages are outside of the set limits.
UNITOUR monitors the input currents of all 3 input phases and the neutral. You can set a
current warning alarm for each input phase and the neutral. An alarm is activated if a warning
level is reached.
From the f
rom the “Home Menu” tap
LOG IN
,
ADVANCED
,
SET POWER LIMITS
.