Chapter 9 Remote Communication Control
73
(3) Connecting
(a) Select Rnet, Fdnet, Cnet, FEnet, FDEnet by the remote 1 network type.
(b) [Fig. 9-4] shows remote 1 through FEnet.
(c) Select XGL-Enet.
(4) Base No.
(a) Assign Base No. that is installed with FEnet I/F module for remote connection.
(5) IP address
(a) FEnet I/F module IP that installed in destination station PLC for remote 1 in network 1
(b) Assign address. [Fig.9-4] shows the connection to FEnet I/F module of IP address 168.192.12.13.
(6) Slot
(a) It shows the position of communication module which is connected to network 1 from local PLC by RS-232C.
(b) In [Fig. 9-4], FEnet I/F module is installed in PLC A. Select the slot no.0.
(c) Select enter on (b), then select connection online menu.
(d) The status of finishing remote 1 is same as the logical connection status with local connection by moving
RS-232C cable.
(e) User can use all function of online menu. (But user can’t do when the type of PLC and present open project
CPU are not matched)
Remark
1) Caution for remote connection
Do remote connection after programming which is for the destination CPU type. If the CPU type is
not a right match, it only do limited functions, it can not do program upload, download and monitoring.