Chapter 5 Protocols of Various Services
32
(b) Response
Classification
Size
Range
Function code
1 byte
0x06
Start address
2 bytes
0x0000 ~ 0xFFFF
Output value
2 bytes
0x0000 or 0xFFFF
[Table 5-38] Function code 0x06 response frame
(c) Error
Classification
Size
Range
Function code
1 byte
0x86 (Function code + 0x80)
Exception code
1 byte
0x01,0x02,0x03,0x04
[Table 5-39] Function code 0x06 error frame
(d) Examples
Request frame
Response frame
Classification
HEX
Classification
HEX
Function code
0x06
Function code
0x06
Start address (Upper byte)
0x00
Number of bytes
0x00
Start address (Lower byte)
0x01
Coil status (27-20)
0x01
Input status (Upper byte)
0x00
Coil status (36-28)
0x00
Number of coils(Lower byte)
0x03
Coil status (38-36)
0x03
[Table 5-40] Function code 0x06 frame examples
(8) Function code 0x10: Write Multiple Registers
(a) Request
Classification
Size
Range
Function code
1 byte
0x10
Start address
2 bytes
0x0000 ~ 0xFFFF
Number of
output
2 bytes
0x0001 or 0x07D8
Number of bytes 1 byte
2 x N
Output value
N x 2 bytes
value
[Table 5-41] Function code 0x10 request frame
(b) Response
Classification
Size
Range
Function code
1 byte
0x10
Number of bytes 2 bytes
0x0000 ~ 0xFFFF
Number of
output
2 bytes
0x0001 ~ 0x007B
[Table 5-42] Function code 0x01 response frame
(c) Error
Classification
Size
Range
Function code
1 byte
0x90 (Function code + 0x80)
Exception code
1 byte
0x01,0x02,0x03,0x04
[Table 5-43] Function code 0x10 error frame