L-INX/L-GATE User Manual
103
LOYTEC
LOYTEC electronics GmbH
Optional ports not necessary for the primary product function. They can be disabled as
described in the installation instructions in Section 12.1:
21 tcp: This port is opened by the FTP server. The port can be changed and disabled.
22 tcp: This port is opened by the SSH server. The port can be changed and disabled.
23 tcp: This port is opened by the Telnet server. The port can be changed and disabled.
161 tcp: This port is opened by the SNMP server. This port is disabled by default. The
port can be changed.
443 tcp: This port is opened by the secure Web server for HTTPS. It can be disabled.
5900 tcp: This port is opened by the VNC server, if it is enabled. This port is disabled
by default. The port can be changed.
502 tcp: This port is opened, if Modbus TCP is configured in slave mode. This port is
disabled by default. The port can be changed.
3671 udp: This port is opened by KNXnet/IP, if KNX is enabled on the Ethernet
interface. This port is disabled by default. The port can be changed.
1630 udp/tcp: This port is used by the CEA-709 RNI and for the remote LPA. The port
can be changed and disabled.
2048 tcp: This port is opened by the logiCAD online test. It cannot be changed. The
service can be disabled but the port will remain open.
16028/16029 udp: These ports are opened for LIOB-IP on the device. These ports cannot
be changed. They can be disabled.
2002 tcp: This port is opened by the Wireshark protocol analyzer front-end. This port is
disabled by default. The port can be changed.
4840 tcp: This port is opened by the OPC UA server. This port is disabled by default.
The port can be changed.
12.4 Services
Required services:
CEA-852 (LON over IP): Primary function of the device. This service is in accordance
with the standard ANSI/CEA-852-B.
BACnet/IP: Primary function of the device. This service is in accordance with the
standard ANSI/ASHRAE 135-2010.
OPC XML-DA: This Web service provides access to data points over the OPC XML-
DA standard.
Optional services not necessary for the primary product function. They can be disabled as
described in the installation instructions in Section 12.1:
HTTP: Web server. It provides a Web-based configuration UI. The Web UI can be
disabled after setting up the device. The Web service is also used for the Configurator
connection for configuration, firmware upgrade, and access to the log file.
HTTPS: Secure Web server. It provides a Web-based configuration UI using HTTPS. It
is also used for a secure Configurator connection.
SSH: SSH server. It provides secure access to the device console menu over the network.
FTP and Telnet: The FTP and Telnet server is used for connection to the device by the
Configurator for configuration, firmware upgrade, and access to the log file. On devices
without SSH these services must be enabled during device configuration.