6 TECHNICAL DATA
6.1 STANDARDS AND OPERATING CONDITIONS
Conformities
CE 2014/35/EU Low-Voltage Directive
2014/30/EU EMC Directive (reference: CE-typical drive system)
EAC TR TC 004/2011 Eurasian conformity: Safety of low voltage equipment
TP TC 020/2011 Eurasian conformity: Electromagnetic compatibility of technical means
RoHS2 2011/65/EU Restrictions for the use of specific hazardous materials in electric and electronic devices
Approvals
cULus UL 61800-5-1, CSA 22.2 No. 274
RCM
EAC
Energy efficiency
Class IE2 EN 50598-2
Type of protection
IP20 EN 60529
Type 1 NEMA 250 Protection against contact
Insulation resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m a.m.s.l.
Overvoltage category II EN 61800-5-1 Above 2000 m a.m.s.l.
Control circuit isolation
Safe mains isolation by double/ EN 61800-5-1
reinforced insulation
Protective measures against
Short circuit
Earth fault Earth fault strength depends on the operating status
Overvoltage
Motor stalling
Motor overtemperature PTC or thermal contact, I
2
xt monitoring
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulations and safety instructions!
Mains switching
3-time mains switching in 1 min Cyclic, without restrictions
Starting current
≤
3 x rated mains current
Mains systems
TT
TN
IT Apply the measures described for IT systems!
Operation on public supply systems
Implement measures to limit The compliance with the requirements for the machine/plant is the responsibility of the manufacturer
the radio interference to be expected: of the machine or plant!
< 0.5 kW: with mains choke EN 61000-3-2
0.5 ... 1 kW: With active filter EN 61000-3-2
> 1 kW at mains current
≤
16 A: EN 61000-3-2
without additional measures
Mains current > 16 A: with mains choke EN 61000-3-12 RSCE: Short-circuit power ratio at the connection point of the machine/plant to the public network.
or mains filter, with dimensioning for rated
power. Rsce
≥
120 is to be met.
Requirements to the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shield < 75/150 pF/m
≤
2,5 mm
2
/ AWG 14
C-core-core/C-core-shield < 150/300 pF/m
≥
4 mm
2
/ AWG 12
Electric strength
Uo/U = 0,6/1,0 kV Uo = r.m.s. value external conductor to PE
U = r.m.s. value external conductor/external conductor
U
≥
600 V UL U = r.m.s. value external conductor/external conductor
Climate
1K3 (-25 ... +60 °C) EN 60721-3-1 Storage
2K3 (-25 ... +70 °C) EN 60721-3-2 Transport
3K3 (-10 ... +55 °C) EN 60721-3-3 Operation
Operation at a switching frequency of 2 or 4 kHz: above +45°C, reduce rated output current by 2.5 %/°C
Operation at a switching frequency of 8 or 16 kHz: above +40°C, reduce rated output current by 2.5 %/°C
Содержание VLB Series
Страница 5: ...I472 GB I 01 19 31100284 G B 3 ELECTRICAL INSTALLATION 3 1 CONNECTION PLAN 5...
Страница 75: ...I472 GB I 01 19 31100284 75 VLB3 1 5kW 2 2kW VLB3 4kW 5 5kW All dimensions in mm Dimensioni in mm...
Страница 76: ...I472 GB I 01 19 31100284 76 VLB3 7 5kW 11kW VLB3 15kW 22kW All dimensions in mm Dimensioni in mm...
Страница 77: ...I472 GB I 01 19 31100284 77 VLB3 30kW 45kW VLB3 55kW 75kW All dimensions in mm Dimensioni in mm...
Страница 78: ...I472 GB I 01 19 31100284 78 VLB3 90kW 110kW All dimensions in mm Dimensioni in mm...