Rated power kW 90 110
Cable installation in compliance with EN 60204-1
Laying system F
Operation
Fuse
Characteristics ––
Max. rated current A ––
Circuit breaker
Characteristics ––
Max. rated current A ––
Operation With mains choke
Fuse
Characteristics gR
Max. rated current A 300
Circuit breaker
Characteristics ––
Max. rated current A ––
Earth-leakage circuit breaker
3-phase mains connection
≥
300 mA, type B
Mains connection
Connection X100
Connection type Screw terminal
Min. cable cross-section mm² ––
Max. cable cross-section mm² 150
Stripping length mm 28
Tightening torque Nm 18
Required tool Allen key 8.0
Motor connection
Connection X105
Connection type Screw terminal
Min. cable cross-section mm² ––
Max. cable cross-section mm² 150
Stripping length mm 28
Tightening torque Nm 18
Required tool Allen key 8.0
PE connection
Connection PE
Connection type PE bolt
Min. cable cross-section mm² ––
Max. cable cross-section mm² 150
Stripping length mm ––
Tightening torque Nm 10
Required tool Key 13
3.3 DC-BUS voltage operative range
Rated mains voltage DC-Bus voltage range
400...480VAC 480...750VDC
Содержание VLB Series
Страница 5: ...I472 GB I 01 19 31100284 G B 3 ELECTRICAL INSTALLATION 3 1 CONNECTION PLAN 5...
Страница 75: ...I472 GB I 01 19 31100284 75 VLB3 1 5kW 2 2kW VLB3 4kW 5 5kW All dimensions in mm Dimensioni in mm...
Страница 76: ...I472 GB I 01 19 31100284 76 VLB3 7 5kW 11kW VLB3 15kW 22kW All dimensions in mm Dimensioni in mm...
Страница 77: ...I472 GB I 01 19 31100284 77 VLB3 30kW 45kW VLB3 55kW 75kW All dimensions in mm Dimensioni in mm...
Страница 78: ...I472 GB I 01 19 31100284 78 VLB3 90kW 110kW All dimensions in mm Dimensioni in mm...