Relay output
Relay is not suitable for direct switching of an electromechanical holding brake! Use a corresponding suppressor circuit in case of an inductive or capacitive load!
Connection Terminal X9: COM Centre contact (common)
Terminal X9: NC Normally-closed contact
Terminal X9: NO Normally-open contact
Minimum DC contact load
Voltage V 10 A correct switching of the relay contacts needs both values
Current mA 10 to be exceeded simultaneously.
Switching voltage/switching current
Maximum AC 240 V A 3 According to UL: General Purpose
DC 24 V A 2 According to UL: Resistive
DC 240 V A 0.16
i
X9
CO
M
NC
NO
PTC input
In the Lovato Electric setting, motor temperature monitoring is activated! In the delivery status, there is a wire jumper between the terminals T1 and T2.
Before connecting a thermal sensor, remove the wire jumper.
Use Connection of PTC or thermal contact
Connection Terminal X109: T1
Terminal X109: T2
Sensor types PTC single sensor (DIN 44081)
PTC triple sensor (DIN 44082)
Thermal contact
i
X109
T1
T2
Terminal description Relay output PTC input Control terminals
Connection X9 X109 X3
Connection type Screw terminal Screw terminal Spring terminal
Min. cable cross-section mm
2
0.5 0.5 0.5
Max. cable cross-section mm
2
1.5 1.5 1.5
Stripping length mm 6 6 9
Tightening torque Nm 0.2 0.2 ––
Required tool 0.4x2.5 0.4x2.5 0.4x2.5
Data of control connections
Содержание VLB Series
Страница 5: ...I472 GB I 01 19 31100284 G B 3 ELECTRICAL INSTALLATION 3 1 CONNECTION PLAN 5...
Страница 75: ...I472 GB I 01 19 31100284 75 VLB3 1 5kW 2 2kW VLB3 4kW 5 5kW All dimensions in mm Dimensioni in mm...
Страница 76: ...I472 GB I 01 19 31100284 76 VLB3 7 5kW 11kW VLB3 15kW 22kW All dimensions in mm Dimensioni in mm...
Страница 77: ...I472 GB I 01 19 31100284 77 VLB3 30kW 45kW VLB3 55kW 75kW All dimensions in mm Dimensioni in mm...
Страница 78: ...I472 GB I 01 19 31100284 78 VLB3 90kW 110kW All dimensions in mm Dimensioni in mm...