I472 GB I 01 19
31100284
9
G
B
Rated power kW 18.5 22 30 37
Cable installation in compliance with EN 60204-1
Laying system B2 C
Operation Without mains choke
Fuse
Characteristics gG/gL or gRL -
Max. rated current A 63 - - -
Circuit breaker
Characteristics B -
Max. rated current A 63 - - -
Operation With mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 63 63 80 100
Circuit breaker
Characteristics B
Max. rated current A 63 63 80 100
Earth-leakage circuit breaker
3-phase mains connection
≥
300 mA, type B
Mains connection
Connection X100
Connection type Screw terminal
Min. cable cross-section mm² 1.5 10
Max. cable cross-section mm² 35 50
Stripping length mm 18 19
Tightening torque Nm 3.8 4
Required tool 0.8 x 5.5 Allen key 4.0
Motor connection
Connection X105
Connection type Screw terminal
Min. cable cross-section mm² 1.5 10
Max. cable cross-section mm² 35 50
Stripping length mm 18 19
Tightening torque Nm 3.8 4
Required tool 0.8 x 5.5 Allen key 4.0
PE connection
Connection PE
Connection type PE screw
Min. cable cross-section mm² 1.5
Max. cable cross-section mm² 25
Stripping length mm 16
Tightening torque Nm 4
Required tool PZ2
Содержание VLB Series
Страница 5: ...I472 GB I 01 19 31100284 G B 3 ELECTRICAL INSTALLATION 3 1 CONNECTION PLAN 5...
Страница 75: ...I472 GB I 01 19 31100284 75 VLB3 1 5kW 2 2kW VLB3 4kW 5 5kW All dimensions in mm Dimensioni in mm...
Страница 76: ...I472 GB I 01 19 31100284 76 VLB3 7 5kW 11kW VLB3 15kW 22kW All dimensions in mm Dimensioni in mm...
Страница 77: ...I472 GB I 01 19 31100284 77 VLB3 30kW 45kW VLB3 55kW 75kW All dimensions in mm Dimensioni in mm...
Страница 78: ...I472 GB I 01 19 31100284 78 VLB3 90kW 110kW All dimensions in mm Dimensioni in mm...