Rated power kW 5.5 7.5 11 15
Cable installation in compliance with EN 60204-1
Laying system B2
Operation Without mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 25 32 32 63
Circuit breaker
Characteristics B
Max. rated current A 25 32 32 63
Operation With mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 25 32 32 63
Circuit breaker
Characteristics B
Max. rated current A 25 32 32 63
Earth-leakage circuit breaker
3-phase mains connection
≥
300 mA, type B
Mains connection
Connection X100
Connection type Screw terminal
Min. cable cross-section mm² 1.5
Max. cable cross-section mm² 6 16 35
Stripping length mm 9 11 18
Tightening torque Nm 0.5 1.2 3.8
Required tool 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
Motor connection
Connection X105
Connection type Screw terminal
Min. cable cross-section mm² 1.5
Max. cable cross-section mm² 6 16 35
Stripping length mm 9 11 18
Tightening torque Nm 0.5 1.2 3.8
Required tool 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
PE connection
Connection PE
Connection type PE screw
Min. cable cross-section mm² 1.5 1.5 1.5
Max. cable cross-section mm² 6 16 25
Stripping length mm 10 11 16
Tightening torque Nm 2 3.4 4
Required tool Torx 20 PZ2
Содержание VLB Series
Страница 5: ...I472 GB I 01 19 31100284 G B 3 ELECTRICAL INSTALLATION 3 1 CONNECTION PLAN 5...
Страница 75: ...I472 GB I 01 19 31100284 75 VLB3 1 5kW 2 2kW VLB3 4kW 5 5kW All dimensions in mm Dimensioni in mm...
Страница 76: ...I472 GB I 01 19 31100284 76 VLB3 7 5kW 11kW VLB3 15kW 22kW All dimensions in mm Dimensioni in mm...
Страница 77: ...I472 GB I 01 19 31100284 77 VLB3 30kW 45kW VLB3 55kW 75kW All dimensions in mm Dimensioni in mm...
Страница 78: ...I472 GB I 01 19 31100284 78 VLB3 90kW 110kW All dimensions in mm Dimensioni in mm...