Doc: I437GB04_16.docx 09/03/2016
p. 27 / 37
68
Sync 2<->3
Active during synchronization between SRC2 and SRC3
69
Sync 3<->1
Active during synchronization between SRC3 and SRC1
Programmable outputs default
Output
Terminals Default function
OUT1
55-56
Open breaker Line 1 (BRK1)
OUT2
56-57 Close contactor/breaker line 1 (BRK1)
OUT3
58-59
Open breaker Line 2 (BRK2)
OUT4
59-60 Close contactor/breaker line 2 (BRK2)
OUT5
61-62
Open breaker Line 3 (BRK3)
OUT6
62-63 Close contactor/breaker line 3 (BRK3)
OUT7
19-20-21
Global alarm A
OUT8
28-29
ATS Ready
OUT9
30-31-32
Control genset 1
OUT10
33-34-35
Control genset 2
OUT11
36-37-38
Control genset 3
System layout
The possible system layouts supported by the ATL900 are listed below. The following information is provided for each one:
The code used for selecting the layout type in the parameter setting P02.01 of the GENERAL menu (example: B: 2S-1T-PL)
An example of synoptic
A truth table
A description of a typical application.
Codes are used by way of examples in these synoptic to identify the single elements. Note that the text of these codes can be freely programmed to make them
correspond to the real system. In our examples, the code indicate the following:
SRCx = SOURCE power line Corresponding to the SRCx power lines.
BRKx = Line breaker. Corresponding to the BRKn breakers.
TBx = Tie Breaker.
LOADx = User load.
NPL = Non-Priority Load.
Case A: 2S – 0T
Case B: 2S - 1T - PL
Case C: 2S – 1T - SI
SRC1
SRC2
BRK1
BRK2
SRC1
SRC2
BRK1
BRK2
TB1
SRC1
SRC2
BRK1
BRK2
TB1
0
0
Open
Open
0
0
Open
Open
Open
0
0
Open
Open
Open
0
1
Open
Closed
0
1
Open
Closed
Open
0
1
Open
Closed
Closed
1
x
Closed
Open
1
x
Closed
Open
Closed
1
0
Closed
Open
Closed
1
1
Closed
Closed
Open
Two
sources
with
only
one
load.
Two
sources
with
one
tie
breaker.
Load
split
between
priority
and
non
‐
priority
(NPL).
Source
2
may
power
only
the
priority
load
(LOAD).
Two
sources
with
one
tie
breaker.
Two
independent
loads
normally
each
powered
by
its
own
source.
If
one
of
the
sources
is
lost,
the
other
source
powers
both
loads.
Case
D:
2S
–
1T
‐
AI
Case
E:
3S
– 0T
SRC1
SRC2
BRK1
BRK2
TB1
SRC1
SRC2
SRC3
BRK1
BRK2
BRK3
0
0
Open
Open
Open
0
0
0
Open
Open
Open
0
1
Open
Closed
Open
1
x
x
Closed
Open
Open
1
0
Closed
Open
Closed
0
1
x
Open
Closed
Open
1
1
Closed
Closed
Open
0
0
1
Open
Open
Closed
Two
sources
with
one
tie
breaker.
Two
independent
loads
normally
each
powered
by
its
own
source.
If
source
SRC2
is
lost,
SRC1
may
power
both
loads
while
SRC2
can
only
power
its
own
load.
Three
sources
with
only
one
load.