background image

 

 

         Doc: I437GB04_16.docx                                      09/03/2016 

p. 15 / 37

 

 

M08 -  SWITCH 

Unit 

Default 

Range

 

P08.01 

Transfer device type     

 

Pulse control breakers 

 

Pulse control brk. 

Continuous control brk. 

Contactor 

P08.02 

Transfer strategy 

 

OBP OBP 

OAP 

P08.03 

Maximum load not powered time 
(alarm A09 tripping delay) 

sec 

60 

OFF / 1…3600 

P08.04 

Automatic return on priority line inhibition 

 

OFF 

OFF / ON 

P08.05 

Genset start delay 

sec 

OFF 

OFF / 1-6000 

P08.06 

Genset rotation interval 

 

OFF 

OFF   
1h-2h-3h- 
 4h-6h-8h- 
12h- 
1d-2d-3d  
4d-5d-6d-7d 

P08.07 

Genset rotation time 

0 0...23/OFF 

P08.08

 

Genset rotation minutes 

min 

0 0...59 

P08.09

 

Distance between genset startups 

sec 

15 0-9999 

P08.10

 

EJP operating mode 

 

Normal Normal 

EJP 

EJP-T 

SCR 

P08.11

 

EJP start delay 

min 

25 0-240 

P08.12

 

EJP switch delay 

min 

5 0-240 

P08.13

 

EJP re-switch block  

 

ON 

OFF / ON 

P08.14 

Closed transition enable    

 

OFF OFF 

ON 

OFF-SYNC 

P08.15 

Max. V delta   

5 0 

- 25 

P08.16 

Max. Hz delta   

Hz 

0.5 0.0 

- 10.0 

P08.17 

Max. Phi delta   

° 

5.0 0.0 

- 10.0 

P08.18 

Synchronisation dwell time    

sec 

0.50 0.00 

-  10.00 

P08.19 

Max. synchronisation time    

sec 

60 0 

- 1000 

P08.20 

Instantaneous parallel time   

sec 

0.25 0.01 

– 5.00 

P08.21 

Increase-decrease voltage/frequency pulse ON time  

sec 

0.5 0.1-10.0 

P08.22 

Increase-decrease voltage/frequency pulse OFF time  

sec 

1.0 

OFF / 0.1-10.0 

P08.01

 - This defines the transfer device type for power lines valid for all breakers BRKn defined in menu M07.  

Pulse breaker

 = Motorised breakers with pulse 

control. 

Continuous breaker 

= motorised breakers with continuous control. 

Contactor

 = Contactor coil control. 

P08.02 - 

This defines the transfer strategy.

 OBP

 = (Open Before Presence) this means that in automatic mode the opening control of a switch is generated when the 

line is beyond the limits regardless of the alternative line state. 

OAP

 = (Open After Presence) this means that in automatic mode the opening control of a 

breaker is only sent after an alternative line is present in the limits. 

P08.03 - 

If in automatic mode all the sources are simultaneously non available for longer than this time alarm 

A09 load timeout not powered

P08.04 - 

If

 

this parameter is enabled after a transfer to an alternative line the return on the priority line does not occur automatically when it is re-established but 

must be controlled in manual mode. 

OFF

 = Automatic return 

ON

 = Return to manual.

 

P08.05 

- Motor start-up delay when the priority line is not within the set limits. If it is set to OFF, the starting cycle starts at the same time as the opening of the 

priority line breaker. 

P08.06 - P08.07 - P08.08 - 

These parameters allow a timed rotation in the application with multiple gensets exchanging the priority between the gensets. P08.06 

defines the rotation interval between the gensets. The day of the day at which the rotation will occur is defined by P08.07 and P08.08. If the rotation range 
is higher than 24h, then the rotation always occurs at the indicated time every n days. If it is lower than 24h, then it occurs at the indicated time and in the 
sub-multiples. For example, if the time is set to 12:30 with the rotation every 6h, there will be a rotation at 12:30, one at 18:30, one at 0:30 etc. 

P08.09 - 

This defines the time which separates the starting for one unit from the following one. If this time elapses after sending a start control without having 

detected the presence of voltage, alarm 

A2n Line n genset not available

 is generated and the system starts a second genset, where available. 

P08.10

 - This defines the EJP operating mode. 

Normal

 = Standard opening mode in AUT mode. 

EJP

 = Two programmable inputs are used set with Start remote 

load off and remote transfer for operation as EJP. When the start input is closed, the motor start delay time (P08.11) is activated at the end of which time 
the starting cycle is run. Subsequently, when the transfer enable is received, is the generated started correctly, the load is transferred from the main line to 
the genset line. The load goes back to the priority line when the transfer enable opens and the genset runs the start cycle when the start input opens. The 
EJP function is enabled only if the system is in automatic mode. The protections and alarms work as usual. 

EJP-T

 = The EJP/T function is a simplified 

variant of the previous EJP, where the genset start-up is controlled identically, but the load is transferred in timed manner instead of with a specific external 
signal. This function thus uses a single digital input, i.e. the starting input. The transfer delay time starts from when the starting control is closed and can be 
set by means of parameter P08.12. 

SCR

 = The SCR function is very similar to the EJP function. In this mode, the start input enables the genset start up as 

EJP, but without waiting for the start delay time P08.11. The remote transfer input has the function of enabling the transfer which occurs after the transfer 
delay P08.12. 

P08.11 - 

Delay between arrival of the EJP genset start signal and the actual start signal. 

P08.12 - 

Load switch delay from priority line to secondary line in EJP and SCR mode. 

P08.13 - 

If ON, in EJP mode, EJP-T and SCR the load is not transferred back on the priority line in case of genset failure but only when the signals on the EJP 

inputs enable them. 

P08.14

 - Closed transition enable. This allows to define how the load will be transferred between two power sources, which are both present. 

OFF

 = the load will be 

transferred with transition open (default). 

ON

 = the two sources are synchronised (where possible) or spontaneous synchronisation will be expected within 

a limit time. The synchronisation thresholds are defined by parameters P08.15 - P08.16 - P08.17 - P08.18. In presence of all synchronisation conditions 
the load will be transferred with closed transition and instantaneous parallel. Obviously, the breakers and external protections must be appropriately 
configured in this case. 

IN-PHASE

 = In this case, the synchronisation conditions will be sought but transfer will occur in all cases with the transition open. 

In this case, the load is passed to a new source the amplitude and phase of which is synchronised with the previous one. 

P08.15

 - Maximum voltage difference between the two sources to be synchronised expressed as a percentage of the rated voltage. 

P08.16

 - Maximum frequency difference between the two sources to be synchronised. 

P08.17

 - Maximum phase angle difference between the two sources to be synchronised. 

P08.18

 - Minimum simultaneous dwell time between the three previous conditions before the synchronism is considered reliable. 

P08.19

 - Maximum waiting time for the synchronisation conditions. After this time, an open transition is performed. 

P08

.

20

 - Instantaneous parallel time in closed transition. 

Содержание ATL900

Страница 1: ...sword protected access 4 Navigating the display pages 4 Synoptic 4 Display pages table 5 Expandability 6 Additional resources 6 Communication channels 7 Inputs outputs internal variables counters analog inputs 7 Limit thresholds LIMx 7 Remote variables REMx 7 User alarms UAx 8 PLC logic PLCx 8 Timers TIMx 8 Automatic test 8 Keypad lock 8 IR programming port 9 Parameter setting from PC 9 Parameter ...

Страница 2: ...esholds with programmable hysteresis Possibility of transferring load with closed transition and spontaneous or controlled genset synchronisation 100 240Vac auxiliary power supply 12 24 48Vdc battery power supply Front optical programming interface Advanced programmable I O functions Integrated programmable PLC logic 50 lines 8 columns Alarm properties entirely definable by the user High accuracy ...

Страница 3: ...parallel There are very many automatic operating cycles which vary according to the defined system configuration 14 possibilities and according to the type of transfer devices used motorised breakers motorised changeover switches or contactors Refer to the possible system configurations and the respective truth tables which describe the system behaviour in automatic mode Note The use of closed tra...

Страница 4: ...be scrolled one at a time The current page is shown on the title bar Some measurements may not be viewed according to the programming and connection of the equipment e g the respective page will not appear if no fuel level sensor is set Some pages have sub pages which can be accessed by pressing e g to view voltages and currents in form of graphic bars The user can specify the page and sub page to...

Страница 5: ...ay pages table PAGES EXEMPLE PAGES EXEMPLE Phase to phase voltage Phase voltage Alarm status Control thresholds Statistics Events list Battery status Expansion modules Inputs and outputs status Inputs Outputs Date Time System info Automatic test ...

Страница 6: ...he basic unit will ask the user to confirm the new configuration If confirmed the new configuration will be saved and become effective Otherwise the discrepancy will be indicated each time the equipment is powered up The current configuration of the system is shown on the specific display page expansion modules indicating the number type and state of the connected modules The I O numbering is list...

Страница 7: ...e internal variable named LIMx will be activated when the measurement is beyond the limits defined by the user by means of the respective setting menu Furthermore up to 8 counters CNT1 CNT8 which can count pulses come from the outside thus from INPx inputs or the number of times for which a given condition occurred For example by defining a LIMx threshold as counting source it will be possible to ...

Страница 8: ...s branches of the ladder logic are stored in internal variables PLCx which may later be used to control the ATL900 outputs or as support memories to built a more complex logic or to control the alarms defined by the user UAx It is additionally possible to create timers inside the PLC program using the programmable timers of the M17 menu The operation of the logic created with the ladder program ma...

Страница 9: ... programming parameters in a simple and innovative way which does not need any connection cable and is able to operate even with non powered ATL900 You can transfer the programming parameters by simply placing a smart device on the front of the ATL900 Operation conditions o The smart device must support the NFC function and have it enabled The smart device must be unlocked Active o If ATL900 is po...

Страница 10: ...tup M04 BATTERY Battery parameters M05 ACOUSTIC ALARMS Control of internal buzzer and external siren M06 SOURCE LINES SRCx Characteristic source data M07 BREAKERS BRKn Characteristic breaker data M08 SWITCH Load transfer mode M09 SOURCE LINE CONTROL SLCx Source line acceptability limits n M10 COMMUNICATIONS Communication parameters M11 AUTOMATIC TEST Period time automatic test mode M12 DIGITAL INP...

Страница 11: ...nt P01 05 Low display backlighting adjustment P01 07 Low display backlighting switch delay P01 08 Reset to default page delay when buttons are not pressed If set to OFF the last manually selected page will always remain on the display P01 09 Default page shown on the display when it is switched on and after the delay P01 10 Free text with alphanumeric name identifying the specific system M02 GENER...

Страница 12: ...rol Direct L1 L2 L3 Inverted L3 L2 L1 Note The corresponding alarms must also be enabled P02 07 Connection type choice three phase with without neutral two phase or single phase P02 08 Voltage controls on concatenated voltages phase voltages or both P02 09 Rated system frequency P02 10 CT positioning for reading currents and powers OFF CT not used LOAD CT positioned on load S1 S2 S3 CT positioned ...

Страница 13: ...arger 3 communication OFF OFF 01 255 P04 01 Rated battery voltage If set to OFF disables the battery state alarms and messages on the display P04 02 MAX battery voltage alarm tripping threshold P04 03 MIN battery voltage alarm tripping threshold P04 04 Tripping delay between MIN and MAX battery alarms P04 05 P04 06 P04 07 P04 08 Serial communication enabling between ATL900 and any BCG RS series co...

Страница 14: ...uous control in RESET OFF mode NOC OFF NOC P07 n 07 Breaker following no closing with feedback open only OFF OFF ON P07 n 08 Minimum coil opening pulse time sec 1 0 0 1 10 0 P07 n 09 Delay between min coils and spring load sec 0 2 0 1 10 0 P07 n 10 Closing retry AUT OFF AUT AUT MAN CLOSING P07 n 11 Breaker conditional enable OFF OFF INPx OUTx LIMx REMx PLCx Ax UAx P07 n 12 Function index x OFF OFF...

Страница 15: ...after sending a start control without having detected the presence of voltage alarm A2n Line n genset not available is generated and the system starts a second genset where available P08 10 This defines the EJP operating mode Normal Standard opening mode in AUT mode EJP Two programmable inputs are used set with Start remote load off and remote transfer for operation as EJP When the start input is ...

Страница 16: ...spective reset hysteresis P09 n 05 cannot be set to a value higher than P09 n 04 By setting P09 n 04 to OFF the maximum voltage control is disabled P09 n 06 defines the maximum voltage tripping delay P09 n 07 Delay time for SRCx to return within the limits used when an alternative threshold is not available Normally shorter than P09 n 08 because the load is not powered and supplying voltage is urg...

Страница 17: ...t to client M11 AUTOMATIC TEST Unit Default Range P11 01 Automatic TEST enable group 1 OFF OFF ON P11 02 Automatic TEST enable group 2 OFF OFF ON P11 03 Automatic TEST enable group 3 OFF OFF ON P11 04 Interval between TESTS gg 7 1 60 P11 05 Enable TEST for Monday ON OFF ON P11 06 Enable TEST for Tuesday ON OFF ON P11 07 Enable TEST for Wednesday ON OFF ON P11 08 Enable TEST for Thursday ON OFF ON ...

Страница 18: ...tion For example if this parameter is programmed on M O the Operating mode output will be activated when the ATL900si is in MAN or OFF mode M15 LIMIT THRESHOLDS LIMn n 1 16 Unit Default Range P15 n 01 Reference measurement OFF OFF measurements list AINx CNTx P15 n 02 Reference measurement source OFF OFF SRC1 SRC2 SRC3 P15 n 03 Channel no x 1 OFF 1 99 P15 n 04 Function Max Max Min Min Max P15 n 05 ...

Страница 19: ...n 08 Channel number x referred to the previous parameter M17 TIMER TIMn n 1 8 Unit Default Range P17 n 01 Timer source OFF ON INPx OUTx LIMx REMx PLCx Axx UAx RALx P17 n 02 Channel no x 1 1 99 P17 n 03 Delay sec 0 0 0 6000 0 Note This menu is divided into 8 sections for the timers TIM1 8 P17 n 01 Source variable which controls the starting and resetting of the concerned timer P17 n 02 Channel numb...

Страница 20: ...le of 1500 litres Section 3 of this menu referred to AIN3 will be programmed as follows P19 3 01 4 20mA P19 3 02 0 0 x 1 0 litres scale start value corresponding to 4mA P19 3 03 x1 P19 3 04 1500 1500 x 1 1500 litres full scale value corresponding to 20mA P19 3 05 x1 P19 3 06 Tank reserve level P19 3 07 litres M20 ANALOG OUTPUTS AOUn n 1 6 Unit Default Range P20 n 01 Output type OFF OFF 0 20mA 4 20...

Страница 21: ...xample of application User alarm UA3 must be generated by the closing of the input INP5 and must show the Doors open message without opening any breaker In the case set menu section 3 for alarm UA3 P21 3 01 INPx P21 3 02 5 P21 3 03 Doors open P21 3 04 P21 3 05 P21 3 06 OFF Alarms When an alarm occurs an alarm icon will appear on the display together with an ID code and the description of the alarm...

Страница 22: ...ll Glob A All Glob B Block BRK1 Block BRK2 Block BRK3 Siren Inhibit Modem No LCD A01 Battery voltage too low A02 Battery voltage too high A03 BRK1 breaker timeout A04 BRK2 breaker timeout A05 BRK3 breaker timeout A06 Incorrect phase sequence Line SRC1 A07 Incorrect phase sequence Line SRC2 A08 Incorrect phase sequence Line SRC3 A09 Load timeout not powered A10 Local battery charger failure A11 Gen...

Страница 23: ...ne genset ready input A22 SRC2 genset line not available As above referred to SRC2 A23 SRC3 genset line not available As above referred to SRC3 A24 Maintenance hours SRC1 Alarm generated when the maintenance hours related to the SRC1 line reach zero See menu M12 Use the Control menu to restore the operating hours and reset the alarm A25 Maintenance hours SRC2 As above referred to SRC2 A26 Maintena...

Страница 24: ...JP function 15 Start genset 1 In AUT mode when closed overrides starting of genset 1 16 Start genset 2 As above referred to genset 2 17 Start genset 3 As above referred to genset 3 18 Emergency NC contact which if open opens all the breakers and generates alarm A14 Emergency block property of A14 are priority 19 Line SRC1 genset ready When closed indicates that the genset connected to the SRC1 lin...

Страница 25: ...ne SRC2 63 Maximum priority line SRC3 As above referred to line SRC3 64 Tie breaker TB1 feedback Auxiliary contact which informs the ATL of the open closed state of tie breaker TB1 If this signal is not connected ATL considers the state of the tie breaker corresponding to the control output state 65 Tie breaker TB2 feedback As above referred to TB2 66 NPL breaker protection trip The input generate...

Страница 26: ...e SRC3 As above referred to line SRC3 32 Load on Line SRC1 Breaker BRK1 closed 33 Load on Line SRC2 Breaker BRK2 closed 34 Load on Line SRC3 Breaker BRK3 closed 35 Alarms A01 Axx Output energised when alarm Axx is active xx 1 alarm number 36 Alarms UA1 Uax Output energised when alarm Uax is active x 1 8 37 Alarm remoting RGKRR unit control pulse output 38 Timer TIM x Output controlled by state of ...

Страница 27: ...l system In our examples the code indicate the following SRCx SOURCE power line Corresponding to the SRCx power lines BRKx Line breaker Corresponding to the BRKn breakers TBx Tie Breaker LOADx User load NPL Non Priority Load Case A 2S 0T Case B 2S 1T PL Case C 2S 1T SI SRC1 SRC2 BRK1 BRK2 SRC1 SRC2 BRK1 BRK2 TB1 SRC1 SRC2 BRK1 BRK2 TB1 0 0 Open Open 0 0 Open Open Open 0 0 Open Open Open 0 1 Open C...

Страница 28: ...ed Open 1 1 x Closed Closed Open Open Three sources with one tie breaker between SRC1 and SRC2 Load split between priority and non priority NPL Each of the three sources can power both loads In case of presence of SRC1 and at least either SRC2 or SRC3 the loads are powered separately Three sources with one tie breaker between SRC2 and SRC3 Load split between priority and non priority NPL Load NPL ...

Страница 29: ... If the advanced access password was entered the command menu can also be used to perform automatic operations useful for configuring the instrument The following table shows the functions which are available with the command menu divided according to the required access level CODE CONTROL ACCESS LEVEL DESCRIPTION C01 RESET MANTENACE HOURS 1 ADVANCED Reset maintenance interval hours of the breaker...

Страница 30: ... with the automatic procedure as programmed C25 RESET PLC MEMORY ADVANCED Reset PLCx variable status Installation ATL900 is designed to be flat panel mounted Frontal protection of IP65 is guaranteed with correct assembly and optional sealing Insert the system in the panel hole making sure that the seal if present is correctly positioned between the panel and instrument frame Make sure that the cus...

Страница 31: ...GRAMMABLE INPUT BATTERY 12 48VDC SSR OUTPUT 3x F1A S2 16 49 50 52 51 PROGRAMMABLE INPUT PROGRAMMABLE INPUT PROGRAMMABLE INPUT PROGRAMMABLE INPUT 23 A 22 TR 25 24 B SG RS485 20 19 21 55 57 56 OPEN LINE 1 CLOSE LINE 1 6 5 7 8 L2 L1 L3 N LINE 2 INPUT 3x F1A 58 60 59 OPEN LINE 2 CLOSE LINE 2 10 9 11 12 L2 L1 L3 N LINE 3 INPUT 3x F1A 61 63 62 OPEN LINE 3 CLOSE LINE 3 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6...

Страница 32: ...14 S1 2 13 S1 1 S2 17 S2 18 CURRENT 27 26 T3 15A BATTERY 12 48V 55 57 56 OPEN LINE 1 CLOSE LINE 1 OUT 1 OUT 2 L N 54 53 A1 A2 AC AUX SUPPLY STATUS INTERLOCK POWER SUPPLY BRK1 OPENING CLOSING TRIP BRK2 BRK3 L N FROM ATLDPS1 BRK2 BRK3 40 43 39 58 60 59 OPEN LINE 2 CLOSE LINE 2 OUT 3 OUT 4 STATUS INTERLOCK POWER SUPPLY OPENING CLOSING TRIP BRK1 BRK3 41 44 61 63 62 OPEN LINE 3 CLOSE LINE 3 OUT 5 OUT 6...

Страница 33: ...3 15A BATTERY 12 48V 55 57 56 OPEN LINE 1 CLOSE LINE 1 OUT 1 OUT 2 L N 54 53 A1 A2 AC AUX SUPPLY STATUS INTERLOCK POWER SUPPLY BRK1 OPENING CLOSING TRIP BRK2 BRK3 L N FROM ATLDPS1 40 43 39 58 60 59 OPEN LINE 2 CLOSE LINE 2 OUT 3 OUT 4 STATUS INTERLOCK POWER SUPPLY OPENING CLOSING TRIP 4144 61 63 62 OPEN LINE 3 CLOSE LINE 3 OUT 5 OUT 6 STATUS INTERLOCK POWER SUPPLY OPENING CLOSING TRIP 42 45 TB1 TB...

Страница 34: ...OM COM INP 9 INP 10 INP 11 INP 12 LINE 1 LINE 2 S1 1 S1 2 S1 3 S1 4 S2 S2 NC TR A B SG N L3 L2 N L3 L2 L1 19 OUT 7 22 23 24 25 RS485 18 17 16 15 14 13 8 7 6 5 4 3 2 1 CURRENT L1 31 30 28 29 32 39 48 49 50 51 52 27 26 SLOT 1 SLOT 2 SLOT 3 BATTERY LINE3 N L3 L2 L1 12 11 10 9 NO 20 COM 21 OUT 10 34 33 35 OUT 11 37 36 38 INP 1 40 INP 2 41 INP 3 42 INP 4 43 INP 5 44 INP 6 45 INP 7 46 INP 8 47 OUT 1 56 ...

Страница 35: ...Doc I437GB04_16 docx 09 03 2016 p 35 37 Mechanical dimensions and panel cutout ...

Страница 36: ...voltage current transformer 5A Measurement type True RMS TRMS Permanent thermal limit 20 Ie Short duration thermal limit 50A for 1 sec Burden 0 6VA Measurement accuracy AC voltage inputs 0 25 f s 1digit Digital inputs terminals 39 47 and 48 52 Input type negative Input current 8mA Low input signal 2 2V High input signal 3 4V Input signal delay 50ms RS485 serial interface terminals 22 25 Interface ...

Страница 37: ...crew type Wire cross section area min and max 0 2 2 5 mmq 24 12 AWG UL use data Wire cross section area min and max 0 75 2 5 mm 18 12 AWG Tightening torque 0 56 Nm 5 Lbin Housing Installation Flush mount Material Polycarbonate Frontal degree of protection IP40 on front IP65 with optional gasket IP20 on terminals Weight 680g Certifications and compliance Certifications obtained cULus EAC Comply wit...

Отзывы: