and this input must execute control C.07 in the command menu, then P12.n.02 is set to value 7.
P12.n.03
- Contact type selection: NO normally open or NC normally closed.
P12.n.04
- Selected input contact closing delay.
P12.n.05
- Selected input contact opening delay
.
M13 – DIGITAL OUTPUTS
(OUT1…20)
Unit
Default
Range
P13.n.01
OUTn output function
(miscellaneous) (see
Output functions
table
)
P13.n.02
Function index (x)
1
OFF / 1…99
P13.n.03
Normal/reverse output
NOR
NOR / REV
Note: This menu is divided into 20 sections, referred to digital outputs OUT1…OUT20.
The outputs on the basic board are numbered from OUT1..OUT10, while the remaining to the those on the expansion modules.
P13.n.01
– Output function selection (see
Programmable output function table
).
P13.n.02
- Index possibly associated to the function programmed under the previous parameter. Example: If the function of the output is set to the
Alarm Axx
function
and this output must be energised when alarm A16 occurs, then P11.n.02 is set to value 16.
P13.n.03
– This sets the output state when the associated function is not active:
NOR
= de-energised output,
REV
= energised output.
M14 - MISCELLANEOUS
Unit
Default
Range
P14.01
Maintenance interval hours
h
OFF
OFF / 1…99999
P14.02
Maintenance interval operations
OFF OFF
1…99999
P14.03
Operative mode output
OFF OFF
O
M
M - O
A
…
P14.01
- This defines the programmed maintenance frequency, expressed in hours. If set to OFF, this maintenance frequency can be deactivated.
P14.02
- This defines the programmed maintenance frequency, expressed in number of operations. If set to OFF, this maintenance frequency can be deactivated.
P14.03
- This defines in which operating modes to activate the output programmed with the
Operating mode
function. For example, if this parameter is programmed
on M-O, the
Operating mode
output will be activated when the ATL900si is in MAN or OFF mode.
M15 - LIMIT THRESHOLDS
(LIMn, n = 1…16)
Unit
Default
Range
P15.n.01
Reference measurement
OFF OFF-
(measurements list)
AINx
CNTx
….
P15.n.02
Reference measurement source
OFF OFF
SRC1
SRC2
SRC3
P15.n.03
Channel no. (x)
1 OFF/1..99
P15.n.04
Function
Max Max
Min
Min+Max
P15.n.05
Upper threshold
0 -9999
- +9999
P15.n.06
Multiplier
x1 /100
- x10k
P15.n.07
Delay
sec
0 0.0
– 600.0
P15.n.08
Lower threshold
0 -9999
- +9999
P15.n.09
Multiplier
x1 /100
- x10k
P15.n.10
Delay sec
0 0.0
– 600.0
P15.n.11
Home state
OFF OFF-ON
P15.n.12
Memory
OFF OFF-ON
Note: This menu is divided into 16 sections for limit thresholds LIM1..16.
P15.n.01
- This defines which measurements supplied by the ATL900 to apply the limit threshold.
P15.n.02
- If the reference measurement is an electric measurement, this defines whether it refers to the mains or the genset.
P15.n.03
- If the reference measurement is a multichannel internal measurement (e.g. AINx), this defines which channel.
P15.n.04
-
This defines the limit threshold operating mode.
Max
= LIMn active when the measurement is higher than P15.n.03. P15.n.06 is the resetting threshold.
Max
= LIMn active when the measurement is lower than P15.n.06. P15.n.03 is the resetting threshold.
Min+Max
= LIMn active when the measurement is
higher than P15.n.03 or lower than P15.n.06.
P15.n.05
and
P15.n.06 -
These define the upper threshold which is given by the value of P15.n.03 multiplied by P15.n.04.
P15.n.07
- Tripping delay on the upper threshold.
P15.n.08, P08.n.09, P08.n.10
- as above referred to the lower threshold.
P15.n.11
- This allows to reverse the LIMn limit state.
P15.n.12
- This defines whether the threshold remains stored or must be manually reset using the command menu (ON) or whether it resets automatically (OFF).
P16 - COUNTERS
(CNTn, n = 1…8)
Unit
Default
Range
P16.n.01
Counter source
OFF OFF
ON
INPx
OUTx
LIMx
REMx
PLCx
Axx