P02.32-P02.34-P02.36
- Post-transfer output energising time after conclusion of the load transfer from one line to the other.
P02.37-P02.38
– When the breaker command mode is set to Continuous (P08.01 = Continuous control brk), this parameter defines the ATL behaviour when moving
to OFF mode.
OFF
= Command relays are de-energized.
NOC
= Command relays hold their previous status (NO Change).
P02.39, P02.40
– Conditional enable of TB1 tie breaker.
OFF
= Tie breaker is enabled normally.
(Any other setting)
= TB1 tie breaker is enabled only if the
selected variable is active. When the variable is not active, if the tie breaker is open, its closing will be avoided. If the tie breaker is closed, it will be
opened.
P02.41, P02.42
– Like previous parameters, referred to TB2.
M03 - PASSWORD
Unit
Default
Range
P03.01
Enable password
OFF OFF-ON
P03.02
User level password
1000 0-9999
P03.03
Advanced level password
2000 0-9999
P03.04
Remote access password
OFF OFF/1-9999
P03.01
- If set to OFF, password management is deactivated; access to settings and the command menu is free.
P03.02
- With P03.01 active, value to be specified to activate user level access. See Password Access section.
P03.03
- As P03.02, referred to Advanced level access.
P03.04
- If set to a numeric value, it comes the code to be specified via serial line before being able to send remote controls.
M04 - BATTERY
Unit
Default
Range
P04.01
Rated battery voltage
V
AUTO
AUTO
12
24
48
OFF
P04.02
MAX voltage limit
%
130 110-140
P04.03
MIN voltage limit
%
75 60-130
P04.04
MIN/MAX voltage delay
sec
10 0-120
P04.05
Local battery charger communication
OFF
OFF / 01…255
P04.06
Genset battery charger 1 communication
OFF
OFF / 01…255
P04.07
Genset battery charger 2 communication
OFF
OFF / 01…255
P04.08
Genset battery charger 3 communication
OFF
OFF / 01…255
P04.01
- Rated battery voltage. If set to OFF, disables the battery state alarms and messages on the display.
P04.02
- MAX battery voltage alarm tripping threshold.
P04.03
-
MIN battery voltage alarm tripping threshold.
P04.04
- Tripping delay between MIN and MAX battery alarms
.
P04.05-P04.06-P04.07-P04.08
- Serial communication enabling between ATL900 and any BCG…RS series communicating battery chargers. It allows to read the
voltages, charging currents and alarms concerning the corresponding battery charger and to view information on the dedicated video page. ‘Local’ means
the battery charger connected to the battery which powers the ATL900 in DC.
M05 - ACOUSTIC ALARMS
Unit
Default
Range
P05.01
Siren sound mode on alarm
Timed
OFF
Keypad
Timed
Repeated
P05.02
Sound activation time on alarm
sec
30
OFF/1-600
P05.03
Sound activation time before starting
sec
OFF OFF / 1-60
P05.04
Sound activation time on remote control start
sec
OFF OFF / 1-60
P05.05
Sound activation time for no line SRC1
sec
OFF OFF / 1-60
P05.06
Sound activation time for no line SRC2
sec
OFF OFF / 1-60
P05.07
Sound activation time for no line SRC3
sec
OFF OFF / 1-60
P05.08
Acoustic indication device
SIREN OFF
SIREN
BUZZER
SIR
P05.09
Buzzer on key press
sec
0.15 OFF /
0.01-0.50
P05.01
-
OFF
= siren deactivated.
Keypad
= Siren sounds continuously until it is cancelled by pressing a button on the front panel.
Timed
= Sounds for the time
specified in P06.02.
Repeated
= Sounds for the time in P06.02, pause for a triple time, and then repeats cyclically.
P05.02
- Acoustic signal activation time on alarm.
P05.03
- Acoustic signal activation time before any starting of the engine.
P05.04
- Acoustic signal activation time following activation of a remote control via communication channel.
P05.05 - P05.06 - P05.07
- Acoustic signal activation time following lack of power on SRC1/2/3 line.
P05.08
- Acoustic signalling device choice.
P05.09
- Buzzer activation and time following button pressing.