background image

 

 

         Doc: I437GB04_16.docx                                      09/03/2016 

p. 14 / 37

 

M06 - SOURCE LINES 
(SRCx, n=1…3) 

Unit 

Default 

Range

 

P06.n.01 

Source description 

 

SRCx (char*6) 

P06.n.02 

Signal priority 

 

n 1 

– 3 

P06.n.03 

SRCx source type 

 

Mains Mains 

Genset 

P06.n.04 

Genset cooling time 

sec 

120  

1-3600 

 

P06.n.05 

Rated source power 

kW 

1000 1-100000 

P06.n.06 

Max. power use limit 

OFF 

OFF / 1-200 

P06.n.07 

Max. power use delay 

sec 

60 1 

- 9999 

P06.n.08 

Power use return limit 

OFF 

OFF / 1-200 

P06.n.09 

Power use return delay 

sec 

60 1 

- 9999 

P06.n.10 

Power use max. limit for non-priority load disconnection 

OFF 

OFF / 1-200 

P06.n.11 

Power use max. delay for non-priority load disconnection 

sec 

60 1 

- 9999 

P06.n.12 

Power use return limit for non-priority load connection 

OFF 

OFF / 1-200 

P06.n.13 

Power use return delay for non-priority load connection 

sec 

60 1 

- 9999 

Note: This menu is divided into 3 sections for source lines SRC1..3. 

P06.n.01

 - Alphanumeric description on the respective power source line which will be shown on the display synoptic panel. 

P06.n.02

 - Power line priority. In case of simultaneous presence of multiple power lines on the same load, the one with priority 1 is connected. If the line with priority 

1 is not present, the one with priority 2 is used etc. If two sources are programmed with the same priority, the software attribute higher priority to the one 
most on the left. 

P06.n.03

 - This defines the type of power source of the SRCx line. 

Mains

 = The mains symbols is shown on the synoptic panel. 

Genset

 = The genset symbol is 

shown and the start/stop outputs are managed; is sought. 

P06.n.04

 - Maximum cooling cycle time. Example: time which elapses between the load disconnection of the genset and the actual stopping of the engine. 

P06.n.05

 - Max. rated power available on the SRCx source. 

P06.n.06

 - Max. power limit (in percentage) which can be taken from the SRCx line. If this limit is exceeded by the load, the load is transferred onto another source 

line. 

P06.n.07

 - Delay referred to the previous parameter. 

P06.n.08

 - Power value (in percentage) which defines the hysteresis with respect to P06.n.06 for the load return to SRCx. 

P06.n.09

 - Delay referred to the previous parameter. 

P06.n.10

 - 

P06.n.11 - P06.n.12 - P06.n.13

 - Thresholds and delays which define the power levels for connecting and disconnecting the non-priority load. 

 

 

M07 - BREAKERS 
(BRKn, n=1…3) 

Unit 

Default 

Range

 

P07.n.01 

Breaker description 

 

BRKn (char*6) 

P07.n.02 

Interlock time SRCx 

 …  

sec 

6.0  

0.1…1800.0 

P07.n.03 

Breaker operation max. time (alarm delay A03 and A04) 

sec 

5  

1…900 

P07.n.04 

Open pulse time    

sec 

10 0-600 

P07.n.05 

Close pulse time     

sec 

1 0-600 

P07.n.06 

Continuous control in RESET/OFF mode 

 

NOC OFF 

 

NOC  

P07.n.07 

Breaker following no closing (with feedback open only) 

 

OFF OFF 

ON 

P07.n.08 

Minimum coil opening pulse time 

sec 

1.0 

0.1 … 10.0 

P07.n.09 

Delay between min. coils and spring load 
 

sec 

0.2 

0.1 … 10.0 

P07.n.10 

Closing retry 

 

AUT OFF 

AUT  

AUT+MAN 

CLOSING 

P07.n.11 

Breaker conditional enable 

 

OFF OFF 

INPx 

OUTx 

LIMx 

REMx 

PLCx 

Ax 

UAx 

P07.n.12 

Function index (x) 

 

OFF 

OFF / 1…99 

Note: This menu is divided into 3 sections for controlling the source line breakers BRK1..3. 

P07.n.01 - 

Alphanumeric description which identifies the line breaker on the display synoptic panel. 

P07.n.02 - 

Interlock time from the opening instant of the breaker BRKn to the closing of another breaker.

 

P07.n.03 - 

Timeout between sending of a control from a line breaker and the actual execution of the operation.  After having sent an opening or closing control to 

the breaker, alarms A03 or A04 are generated if it is not positioned correctly before the timeout. It works when the auxiliary state contacts of the 
breakers is programmed and wired. 

P07.n.04 - 

Minimum opening control time, when the breaker control is defined by means of a pulse (P08.01 = Pulse  breaker). For applications with motorised line 

breakers, this must be set to a sufficient time to allow complete charging of the springs. This time is considered also when working in continuous control 
mode. 

P07.n.05 - 

Closing control pulse time. 

P07.n.06 – 

Otherwise, the breaker control is selected as continuous (P08.01 = Continuous breaker), defines the behaviour of the board when it switches to the OFF 

operating mode. 

OFF

 = The control relays are de-energised. 

NOC

 = The control relays remain in in their original state (No Change). 

P07.n.07 -

 In case of timeout caused by the line breaker BRKn failing to close (open feedback contact) causes the transfer of the load on an alternative line.

 

P07.n.08 - 

Minimum coil deactivation pulse duration for breaker opening pulse. 

P07.n.09

 - Time elapsed between minimum voltage opening pulse and breaker spring loading control. 

P07.n.10 

- This defines whether in case of failure to close the ATL900 must perform a retry consisting of a cycle of opening/spring recharging cycles followed by a 

new closing attempt. The failed closing alarm will be generated if the second attempt also fails.  

OFF

 = Closing is not retryed.  

AUT

 = Retry is manual only. 

AUT+MAN

 = Retry enabled in both modes. 

CLOSING

 = Closing retry is executed in AUT or MAN only in case of failed closing 

but not when breaker opens unexpectedly. 

P07.n.11, P07.n.12

-  Conditional enable of breaker. 

OFF

 = Breaker is enabled normally. 

(Any other setting)

 = The breaker is enabled only if the selected variable 

is active. When the variable is not active, if the breaker is open, its closing will be avoided. If the breaker is closed, it will be opened. 

 

Содержание ATL900

Страница 1: ...sword protected access 4 Navigating the display pages 4 Synoptic 4 Display pages table 5 Expandability 6 Additional resources 6 Communication channels 7 Inputs outputs internal variables counters analog inputs 7 Limit thresholds LIMx 7 Remote variables REMx 7 User alarms UAx 8 PLC logic PLCx 8 Timers TIMx 8 Automatic test 8 Keypad lock 8 IR programming port 9 Parameter setting from PC 9 Parameter ...

Страница 2: ...esholds with programmable hysteresis Possibility of transferring load with closed transition and spontaneous or controlled genset synchronisation 100 240Vac auxiliary power supply 12 24 48Vdc battery power supply Front optical programming interface Advanced programmable I O functions Integrated programmable PLC logic 50 lines 8 columns Alarm properties entirely definable by the user High accuracy ...

Страница 3: ...parallel There are very many automatic operating cycles which vary according to the defined system configuration 14 possibilities and according to the type of transfer devices used motorised breakers motorised changeover switches or contactors Refer to the possible system configurations and the respective truth tables which describe the system behaviour in automatic mode Note The use of closed tra...

Страница 4: ...be scrolled one at a time The current page is shown on the title bar Some measurements may not be viewed according to the programming and connection of the equipment e g the respective page will not appear if no fuel level sensor is set Some pages have sub pages which can be accessed by pressing e g to view voltages and currents in form of graphic bars The user can specify the page and sub page to...

Страница 5: ...ay pages table PAGES EXEMPLE PAGES EXEMPLE Phase to phase voltage Phase voltage Alarm status Control thresholds Statistics Events list Battery status Expansion modules Inputs and outputs status Inputs Outputs Date Time System info Automatic test ...

Страница 6: ...he basic unit will ask the user to confirm the new configuration If confirmed the new configuration will be saved and become effective Otherwise the discrepancy will be indicated each time the equipment is powered up The current configuration of the system is shown on the specific display page expansion modules indicating the number type and state of the connected modules The I O numbering is list...

Страница 7: ...e internal variable named LIMx will be activated when the measurement is beyond the limits defined by the user by means of the respective setting menu Furthermore up to 8 counters CNT1 CNT8 which can count pulses come from the outside thus from INPx inputs or the number of times for which a given condition occurred For example by defining a LIMx threshold as counting source it will be possible to ...

Страница 8: ...s branches of the ladder logic are stored in internal variables PLCx which may later be used to control the ATL900 outputs or as support memories to built a more complex logic or to control the alarms defined by the user UAx It is additionally possible to create timers inside the PLC program using the programmable timers of the M17 menu The operation of the logic created with the ladder program ma...

Страница 9: ... programming parameters in a simple and innovative way which does not need any connection cable and is able to operate even with non powered ATL900 You can transfer the programming parameters by simply placing a smart device on the front of the ATL900 Operation conditions o The smart device must support the NFC function and have it enabled The smart device must be unlocked Active o If ATL900 is po...

Страница 10: ...tup M04 BATTERY Battery parameters M05 ACOUSTIC ALARMS Control of internal buzzer and external siren M06 SOURCE LINES SRCx Characteristic source data M07 BREAKERS BRKn Characteristic breaker data M08 SWITCH Load transfer mode M09 SOURCE LINE CONTROL SLCx Source line acceptability limits n M10 COMMUNICATIONS Communication parameters M11 AUTOMATIC TEST Period time automatic test mode M12 DIGITAL INP...

Страница 11: ...nt P01 05 Low display backlighting adjustment P01 07 Low display backlighting switch delay P01 08 Reset to default page delay when buttons are not pressed If set to OFF the last manually selected page will always remain on the display P01 09 Default page shown on the display when it is switched on and after the delay P01 10 Free text with alphanumeric name identifying the specific system M02 GENER...

Страница 12: ...rol Direct L1 L2 L3 Inverted L3 L2 L1 Note The corresponding alarms must also be enabled P02 07 Connection type choice three phase with without neutral two phase or single phase P02 08 Voltage controls on concatenated voltages phase voltages or both P02 09 Rated system frequency P02 10 CT positioning for reading currents and powers OFF CT not used LOAD CT positioned on load S1 S2 S3 CT positioned ...

Страница 13: ...arger 3 communication OFF OFF 01 255 P04 01 Rated battery voltage If set to OFF disables the battery state alarms and messages on the display P04 02 MAX battery voltage alarm tripping threshold P04 03 MIN battery voltage alarm tripping threshold P04 04 Tripping delay between MIN and MAX battery alarms P04 05 P04 06 P04 07 P04 08 Serial communication enabling between ATL900 and any BCG RS series co...

Страница 14: ...uous control in RESET OFF mode NOC OFF NOC P07 n 07 Breaker following no closing with feedback open only OFF OFF ON P07 n 08 Minimum coil opening pulse time sec 1 0 0 1 10 0 P07 n 09 Delay between min coils and spring load sec 0 2 0 1 10 0 P07 n 10 Closing retry AUT OFF AUT AUT MAN CLOSING P07 n 11 Breaker conditional enable OFF OFF INPx OUTx LIMx REMx PLCx Ax UAx P07 n 12 Function index x OFF OFF...

Страница 15: ...after sending a start control without having detected the presence of voltage alarm A2n Line n genset not available is generated and the system starts a second genset where available P08 10 This defines the EJP operating mode Normal Standard opening mode in AUT mode EJP Two programmable inputs are used set with Start remote load off and remote transfer for operation as EJP When the start input is ...

Страница 16: ...spective reset hysteresis P09 n 05 cannot be set to a value higher than P09 n 04 By setting P09 n 04 to OFF the maximum voltage control is disabled P09 n 06 defines the maximum voltage tripping delay P09 n 07 Delay time for SRCx to return within the limits used when an alternative threshold is not available Normally shorter than P09 n 08 because the load is not powered and supplying voltage is urg...

Страница 17: ...t to client M11 AUTOMATIC TEST Unit Default Range P11 01 Automatic TEST enable group 1 OFF OFF ON P11 02 Automatic TEST enable group 2 OFF OFF ON P11 03 Automatic TEST enable group 3 OFF OFF ON P11 04 Interval between TESTS gg 7 1 60 P11 05 Enable TEST for Monday ON OFF ON P11 06 Enable TEST for Tuesday ON OFF ON P11 07 Enable TEST for Wednesday ON OFF ON P11 08 Enable TEST for Thursday ON OFF ON ...

Страница 18: ...tion For example if this parameter is programmed on M O the Operating mode output will be activated when the ATL900si is in MAN or OFF mode M15 LIMIT THRESHOLDS LIMn n 1 16 Unit Default Range P15 n 01 Reference measurement OFF OFF measurements list AINx CNTx P15 n 02 Reference measurement source OFF OFF SRC1 SRC2 SRC3 P15 n 03 Channel no x 1 OFF 1 99 P15 n 04 Function Max Max Min Min Max P15 n 05 ...

Страница 19: ...n 08 Channel number x referred to the previous parameter M17 TIMER TIMn n 1 8 Unit Default Range P17 n 01 Timer source OFF ON INPx OUTx LIMx REMx PLCx Axx UAx RALx P17 n 02 Channel no x 1 1 99 P17 n 03 Delay sec 0 0 0 6000 0 Note This menu is divided into 8 sections for the timers TIM1 8 P17 n 01 Source variable which controls the starting and resetting of the concerned timer P17 n 02 Channel numb...

Страница 20: ...le of 1500 litres Section 3 of this menu referred to AIN3 will be programmed as follows P19 3 01 4 20mA P19 3 02 0 0 x 1 0 litres scale start value corresponding to 4mA P19 3 03 x1 P19 3 04 1500 1500 x 1 1500 litres full scale value corresponding to 20mA P19 3 05 x1 P19 3 06 Tank reserve level P19 3 07 litres M20 ANALOG OUTPUTS AOUn n 1 6 Unit Default Range P20 n 01 Output type OFF OFF 0 20mA 4 20...

Страница 21: ...xample of application User alarm UA3 must be generated by the closing of the input INP5 and must show the Doors open message without opening any breaker In the case set menu section 3 for alarm UA3 P21 3 01 INPx P21 3 02 5 P21 3 03 Doors open P21 3 04 P21 3 05 P21 3 06 OFF Alarms When an alarm occurs an alarm icon will appear on the display together with an ID code and the description of the alarm...

Страница 22: ...ll Glob A All Glob B Block BRK1 Block BRK2 Block BRK3 Siren Inhibit Modem No LCD A01 Battery voltage too low A02 Battery voltage too high A03 BRK1 breaker timeout A04 BRK2 breaker timeout A05 BRK3 breaker timeout A06 Incorrect phase sequence Line SRC1 A07 Incorrect phase sequence Line SRC2 A08 Incorrect phase sequence Line SRC3 A09 Load timeout not powered A10 Local battery charger failure A11 Gen...

Страница 23: ...ne genset ready input A22 SRC2 genset line not available As above referred to SRC2 A23 SRC3 genset line not available As above referred to SRC3 A24 Maintenance hours SRC1 Alarm generated when the maintenance hours related to the SRC1 line reach zero See menu M12 Use the Control menu to restore the operating hours and reset the alarm A25 Maintenance hours SRC2 As above referred to SRC2 A26 Maintena...

Страница 24: ...JP function 15 Start genset 1 In AUT mode when closed overrides starting of genset 1 16 Start genset 2 As above referred to genset 2 17 Start genset 3 As above referred to genset 3 18 Emergency NC contact which if open opens all the breakers and generates alarm A14 Emergency block property of A14 are priority 19 Line SRC1 genset ready When closed indicates that the genset connected to the SRC1 lin...

Страница 25: ...ne SRC2 63 Maximum priority line SRC3 As above referred to line SRC3 64 Tie breaker TB1 feedback Auxiliary contact which informs the ATL of the open closed state of tie breaker TB1 If this signal is not connected ATL considers the state of the tie breaker corresponding to the control output state 65 Tie breaker TB2 feedback As above referred to TB2 66 NPL breaker protection trip The input generate...

Страница 26: ...e SRC3 As above referred to line SRC3 32 Load on Line SRC1 Breaker BRK1 closed 33 Load on Line SRC2 Breaker BRK2 closed 34 Load on Line SRC3 Breaker BRK3 closed 35 Alarms A01 Axx Output energised when alarm Axx is active xx 1 alarm number 36 Alarms UA1 Uax Output energised when alarm Uax is active x 1 8 37 Alarm remoting RGKRR unit control pulse output 38 Timer TIM x Output controlled by state of ...

Страница 27: ...l system In our examples the code indicate the following SRCx SOURCE power line Corresponding to the SRCx power lines BRKx Line breaker Corresponding to the BRKn breakers TBx Tie Breaker LOADx User load NPL Non Priority Load Case A 2S 0T Case B 2S 1T PL Case C 2S 1T SI SRC1 SRC2 BRK1 BRK2 SRC1 SRC2 BRK1 BRK2 TB1 SRC1 SRC2 BRK1 BRK2 TB1 0 0 Open Open 0 0 Open Open Open 0 0 Open Open Open 0 1 Open C...

Страница 28: ...ed Open 1 1 x Closed Closed Open Open Three sources with one tie breaker between SRC1 and SRC2 Load split between priority and non priority NPL Each of the three sources can power both loads In case of presence of SRC1 and at least either SRC2 or SRC3 the loads are powered separately Three sources with one tie breaker between SRC2 and SRC3 Load split between priority and non priority NPL Load NPL ...

Страница 29: ... If the advanced access password was entered the command menu can also be used to perform automatic operations useful for configuring the instrument The following table shows the functions which are available with the command menu divided according to the required access level CODE CONTROL ACCESS LEVEL DESCRIPTION C01 RESET MANTENACE HOURS 1 ADVANCED Reset maintenance interval hours of the breaker...

Страница 30: ... with the automatic procedure as programmed C25 RESET PLC MEMORY ADVANCED Reset PLCx variable status Installation ATL900 is designed to be flat panel mounted Frontal protection of IP65 is guaranteed with correct assembly and optional sealing Insert the system in the panel hole making sure that the seal if present is correctly positioned between the panel and instrument frame Make sure that the cus...

Страница 31: ...GRAMMABLE INPUT BATTERY 12 48VDC SSR OUTPUT 3x F1A S2 16 49 50 52 51 PROGRAMMABLE INPUT PROGRAMMABLE INPUT PROGRAMMABLE INPUT PROGRAMMABLE INPUT 23 A 22 TR 25 24 B SG RS485 20 19 21 55 57 56 OPEN LINE 1 CLOSE LINE 1 6 5 7 8 L2 L1 L3 N LINE 2 INPUT 3x F1A 58 60 59 OPEN LINE 2 CLOSE LINE 2 10 9 11 12 L2 L1 L3 N LINE 3 INPUT 3x F1A 61 63 62 OPEN LINE 3 CLOSE LINE 3 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6...

Страница 32: ...14 S1 2 13 S1 1 S2 17 S2 18 CURRENT 27 26 T3 15A BATTERY 12 48V 55 57 56 OPEN LINE 1 CLOSE LINE 1 OUT 1 OUT 2 L N 54 53 A1 A2 AC AUX SUPPLY STATUS INTERLOCK POWER SUPPLY BRK1 OPENING CLOSING TRIP BRK2 BRK3 L N FROM ATLDPS1 BRK2 BRK3 40 43 39 58 60 59 OPEN LINE 2 CLOSE LINE 2 OUT 3 OUT 4 STATUS INTERLOCK POWER SUPPLY OPENING CLOSING TRIP BRK1 BRK3 41 44 61 63 62 OPEN LINE 3 CLOSE LINE 3 OUT 5 OUT 6...

Страница 33: ...3 15A BATTERY 12 48V 55 57 56 OPEN LINE 1 CLOSE LINE 1 OUT 1 OUT 2 L N 54 53 A1 A2 AC AUX SUPPLY STATUS INTERLOCK POWER SUPPLY BRK1 OPENING CLOSING TRIP BRK2 BRK3 L N FROM ATLDPS1 40 43 39 58 60 59 OPEN LINE 2 CLOSE LINE 2 OUT 3 OUT 4 STATUS INTERLOCK POWER SUPPLY OPENING CLOSING TRIP 4144 61 63 62 OPEN LINE 3 CLOSE LINE 3 OUT 5 OUT 6 STATUS INTERLOCK POWER SUPPLY OPENING CLOSING TRIP 42 45 TB1 TB...

Страница 34: ...OM COM INP 9 INP 10 INP 11 INP 12 LINE 1 LINE 2 S1 1 S1 2 S1 3 S1 4 S2 S2 NC TR A B SG N L3 L2 N L3 L2 L1 19 OUT 7 22 23 24 25 RS485 18 17 16 15 14 13 8 7 6 5 4 3 2 1 CURRENT L1 31 30 28 29 32 39 48 49 50 51 52 27 26 SLOT 1 SLOT 2 SLOT 3 BATTERY LINE3 N L3 L2 L1 12 11 10 9 NO 20 COM 21 OUT 10 34 33 35 OUT 11 37 36 38 INP 1 40 INP 2 41 INP 3 42 INP 4 43 INP 5 44 INP 6 45 INP 7 46 INP 8 47 OUT 1 56 ...

Страница 35: ...Doc I437GB04_16 docx 09 03 2016 p 35 37 Mechanical dimensions and panel cutout ...

Страница 36: ...voltage current transformer 5A Measurement type True RMS TRMS Permanent thermal limit 20 Ie Short duration thermal limit 50A for 1 sec Burden 0 6VA Measurement accuracy AC voltage inputs 0 25 f s 1digit Digital inputs terminals 39 47 and 48 52 Input type negative Input current 8mA Low input signal 2 2V High input signal 3 4V Input signal delay 50ms RS485 serial interface terminals 22 25 Interface ...

Страница 37: ...crew type Wire cross section area min and max 0 2 2 5 mmq 24 12 AWG UL use data Wire cross section area min and max 0 75 2 5 mm 18 12 AWG Tightening torque 0 56 Nm 5 Lbin Housing Installation Flush mount Material Polycarbonate Frontal degree of protection IP40 on front IP65 with optional gasket IP20 on terminals Weight 680g Certifications and compliance Certifications obtained cULus EAC Comply wit...

Отзывы: