Doc: I437GB04_16.docx 09/03/2016
p. 30 / 37
C19
SETUP TO DEFAULT
ADVANCED
Resets all the parameters in the setup menu to the default values
C20
SAVE SETUP COPY
ADVANCED
Copies the parameters currently set to a backup for restoring in the future
C21
RELOAD PARAMETERS FROM BACKUP MEMORY
ADVANCED
Transfers the parameters saved in the backup memory to the active
settings memory
C22
FORCED I/O
ADVANCED
Enables test mode so you can manually energize any output.
Warning! In this mode the installer alone is responsible for the
output commands
C23
RESET A03/04/05 ALARMS
ADVANCED
Restores the opening and closing command of the commutation devices
after generating alarms A03 – A04 – A05
C24
SIMULATE LINE FAILURE
ADVANCED
The device moves to AUT mode and simulates the lack of the priority
source for one minute. It then switches the load with the automatic
procedure as programmed
C25
RESET PLC MEMORY
ADVANCED
Reset PLCx variable status
Installation
ATL900 is designed to be flat panel mounted. Frontal protection of IP65 is guaranteed with correct assembly and optional sealing.
Insert the system in the panel hole making sure that the seal, if present, is correctly positioned between the panel and instrument frame.
Make sure that the customisation label is not folded under the seal, which would compromise sealing. The label must be positioned correctly inside the panel.
In the panel, for each of the four fixing clips, place the metallic clip in the hole on the sides of the container and then move it backwards to insert the hook in the seat.
Repeat the operation for the four clips.
Tighten the fixing screw with a maximum torque of 0.5Nm.
If the device must be disassembled, loosen the four screws and reverse the order.
For electric connections, refer to the connection diagrams shown in the specific chapter and the requirements shown in the technical features table.