To meet its policy concerning EMC, based on the Community directives 

2014/30/UE 

2014/35/UE

, the 

LOREME company takes into account the standards relative to this directives from the very start of the con-
ception of each product. 
The set of tests performed on the devices, designed to work in an industrial environment, are made in accor-
dance with 

IEC 61000-6-4 

and 

IEC 61000-6-2 

standards in order to establish the UE declaration of confor-

mity. The devices being in certain typical configurations during the tests, it is impossible to guarantee the re-
sults in every possible configurations. To ensure optimum operation of each device, it would be judicious to 
comply with several recommendations of use. 

 
2) Recommendations of use 
 
2.1 ) General remarks 
 

- Comply with the recommendations of assembly indicated in the technical sheet (direction of assembly, 
spacing between the devices, ...). 
- Comply with the recommendations of use indicated in the technical sheet (temperature range, protection 
index). 
- Avoid dust and excessive humidity, corrosive gas, considerable sources of heat. 
- Avoid disturbed environments and disruptive phenomena or elements. 
- If possible, group together the instrumentation devices in a zone separated from the power and relay cir-
cuits. 
- Avoid the direct proximity with considerable power distance switches, contactors, relays, thyristor power 
groups, ... 
- Do not get closer within fifty centimeters of a device with a transmitter (walkie-talkie) of a power of 5 W, be-
cause the latter can create a field with an intensity higher than 10 V/M for a distance fewer than 50 cm. 

 
2.2 ) Power supply 
 

- Comply with the features indicated in the technical sheet (power supply voltage, frequency, allowance of the 
values, stability, variations ...). 
- It is better that the power supply should come from a system with section switches equipped with fuses for 
the instrumentation element and that the power supply line be the most direct possible from the section 
switch. 
- Avoid using this power supply for the control of relays, of contactors, of electrogates,  ... 
- If the switching of thyristor statical groups, of engines, of speed variator, ... causes strong interferences on 
the power supply circuit, it would be necessary to put an insulation transformer especially intended for instru-
mentation linking the screen to earth. 
- It is also important that the installation should have a good earth system and it is better that the voltage in 
relation to the neutral should not exceed 1V, and the resistance be inferior to 6 ohms. 
- If the installation is near high frequency generators or installations of arc welding, it is better to put suitable 
section filters. 
 

2.3 ) Inputs / Outputs 
 

- In harsh conditions, it is advisable to use sheathed and twisted cables whose ground braid will be linked to 
the earth at a single point. 
- It is advisable to separate the input / output lines from the power supply lines in order to avoid the coupling 
phenomena. 
- It is also advisable to limit the lengths of data cables as much as possible. 

 

 
EMC Consideration 

Содержание IPL36L

Страница 1: ...meter LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Telefax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual at www...

Страница 2: ...nfiguration p8 5 Relays threshold setting visualization p8 RS232 LINK SETTING p9 TERMINAL MODE p10 1 Visualization p10 2 Configuration p10 2 1 Method p10 2 1 1 Menu selection p10 2 1 2 Parameter selec...

Страница 3: ...Visualization At power on the device displays briefly its actual revision number It s a message of the form r x y where x is the hardware revision and y the software revision Then it displays the cur...

Страница 4: ...current input 200 mV 200 A for the external shunt current input default shunt sensitivity is 1 A mV 4000 mV for the Hall sensor current input default configured caliber is 100 A The inputs configurati...

Страница 5: ...ose the three phases mode or the no button to select the previous choice PT RATIO Push the yes button to access the PT ration setting 0 001 to 106 or the no button to go to the next rubric CT RATIO Pu...

Страница 6: ...ergy count no to deactivate it PULSE WEIGHT Push the yes button to access the counting pulse weight parameter 0 01 kWh minimum RELAY 2 Push the yes button to access to the relay 2 configuration only w...

Страница 7: ...es button to access to the rubric Use the buttons to increase decrease the value and the button to validate it The output factory address is 1 BAUD RATE Push the yes button to access to the rubric Use...

Страница 8: ...measure mode without saving the new configuration 5 Setting or displaying the relays threshold If the threshold detection is activated pushing the button accesses to the threshold setting or displayi...

Страница 9: ...another communication port number COMx and re quires the reconfiguration of the HyperTerminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For later ve...

Страница 10: ...ration mode just press C key The message ConF is displayed in front 2 1 Method during the configuration different types of questions are displayed For each one several answers are possible You will fi...

Страница 11: ...eactivate the alarm on threshold overrun Threshold detection parameters are Monitored value voltage current frequency on IPL36 and IPL36L and active power reactive power apparent power power factor on...

Страница 12: ...tion Response time The limitation allows to bound the output signal swing to the configured output scales for any input signal swing over flow The response time allows to smooth the TRMS measure rippl...

Страница 13: ...play mode or N to choose the Y N YES fixed mode in kW kVAR kVA with 2 decimals 2 9 Special function This section allows you to lock the front face configuration access SPECIAL FUNCTION Press Y to acce...

Страница 14: ...Byte first word 1 exponent mantissa MSB word 2 mantissa Data in 32 bits integer signed or not Data send MSB first 4 bytes or 2 words long Data in 16 bits integer format for status of alarm R1 bit0 and...

Страница 15: ...ata The register address are the same as the table for MODBUS TCP This table lists the measures in 32 bits integer format and one 16 bits register for the alarms state address 18 The values given in t...

Страница 16: ...rge A network higher load can cause communication error due to the traffic The average response time to a read request is around 50ms 3 Data explanation All measures are accessible in reading mode Dat...

Страница 17: ...easures are at FFFFFFFF hexadecimal Register address in decimal Hexadecimal Designation Total words 4096 1000 Voltage V Word 1 1 Word 2 2 4098 1002 Current A Word 1 3 Word 2 4 4100 1004 Active Power W...

Страница 18: ...Multiply the values of powers by the PT ratio and the CT ratio or external shunt sensibility and divide the result by 10 000 Register address in decimal Hexadecimal Designation Total words 0 000 Volt...

Страница 19: ...ments of an IPL36 or IPL36L Click to refresh measures version number Tab for SNMP parameters Tab for password configuration IPL36 IPL36L There are no energy power power factor measurement 2 SNMP tab D...

Страница 20: ...re details The MIB file can be downloaded directly on the Web page of the device 3 Security tab Limit the web server access with a password This length of this password is up to 8 characters This char...

Страница 21: ...provide by LOREME and contain the firmware code in Intel HEX format Select the Transfer Send a text file in the HyperTerminal menu Select the directory and open the file The HyperTerminal program beg...

Страница 22: ...elays thyristor power groups Do not get closer within fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher t...

Страница 23: ...ption Analogical output mA terminals analog analog no jumper Analogical output V terminals analog analog need jumper between terminals analog 500 High voltage input terminals 600 V 0V Low voltage inpu...

Страница 24: ...terminals L N Relay 1 terminals common C1 rest R1 work T1 Relay 2 terminals common C2 rest R2 work T2 High voltage input terminals 600 V 0V Low voltage input terminals 150 V 0V Current input terminal...

Отзывы: