SOMMAIRE
E 12
LOREME
12, rue des Potiers d'Etain - 57071 Metz
03.87.76.32.51 - Fax 03.87.76.32.52 - Email: [email protected] - Techni-
The
activation and deactivation delays
, configurable from 0 to 600 s set the time above which alarm changes its state
after event appearance and disappearance.
The
energy count
rubric allows you to activate or deactivate the use of the relay for energy metering.
For this mode, the only parameter to be configured is the counting pulse weight. In this mode, at each count pulse, the
relay is switched on for 150 ms.
2.6) Analogical output
The device can, by the /S option, provide an analogical output, insulated and configurable.
Output parameters:
- Current output (mA).
- Voltage output (V) with strap connected (see wiring
p23
).
- Low and high output scales.
- Monitored value: voltage, current, frequency, on IPL36 and IPL36L
and active power, reactive power, apparent power, power factor, on IPL36.
- Low and high input measure scales.
- Limitation.
- Response time.
The
limitation
allows to bound the output signal swing to the configured output scales for any input signal swing over-
flow.
The
response time
allows to smooth the TRMS measure ripple transmitted on the analogical output signal. It is adjust-
able from 0 to 60 s.
2.7) Setting of communication parameters
2.7.1) MODBUS TCP (option /CMTCP)
The parameters are : IP address, IP mask and gateway address.
2.7.2) MODBUS (option /CM)
The parameters are : Slave address, baud rate and parity.
-
address
: modbus slave address (1 to 255),
-
Baud rate
(1200, 2400, 4800, 9600, 19200, 38400 bauds),
-
parity
(Even, Odd, None).
The measure data are available with different format:
- 32 bits IEEE floating point number.
- 32 bits signed integer, measure x 100.
2.8) Display
This rubric permits to personalize the measurements display on the front.
The display parameters are:
- Display filter.
- Decimal point display mode.
- Power units display mode.
DISPLAY CONFIGURATION?
(Y-N)
Press the ‘Y’ key to access display configuration.
Event
Alarm
Security: relay activated on alarm
Security: relay activated out of alarm
Delay before
Delay before
active
Relay off
Relay on
Relay on
Relay off
inactive