background image

 

SOMMAIRE

 

E 14 

 

LOREME

 12, rue des Potiers d'Etain - 57071 Metz  

 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: [email protected] - Techni-

1) Feature

 

Protocol: 

 

 

MODBUS RTU 

Link:   

 

 

RS485 

Baudrate: 

 

 

1200 to 38400 bds 

Address: 

 

 

1 to 255 

 

 

Reading request:   

function code 03,04 

Type of data: 

 

electrical measurement, status of alarms. 

data format:  

 

Measure in floating point and 32 bits signed or unsigned integer format. 

response time: 

 

The delay for a reading request is <40ms 

 
 

2) Data 
 
2.1) Available data 

All measures are accessible in reading mode. Data's are available in different formats: 
 

- 2 words, 4 bytes, for measures in the 32 bits IEEE floating point format. 

 

- 2 words, 4 bytes, for measures in the 32 bits integer format. 

 

- 1 word, 2 bytes, for the alarms state. 

 
2.2) Format of data

 

- Data in 32 bits IEEE floating point format 
- Data send Most Significant Byte first (word 1: ex mantissa MSB, word 2: mantissa) 

 

 
- Data in 32 bits integer signed or not.  
- Data send MSB first. 4 bytes or 2 words long. 

 
 
 
 
 
 

 
- Data in 16 bits integer format for status of alarm R1 (bit0) and R2 (bit1).  
- Data send MSB first. 

 
 
 
 
 

 
3)

 Exception frame: 

If the slave receive an corrupted frame (CRC16 or parity), it doesn’t answer. If it is a frame error (data address, function, 
value), the slave send a exception frame. The exception frame is a 5 bytes frame long. 
 
Details of the exception frame: The function code of the exception frame is identical to the question frame, but this MSB 
bit is set to 1. The error code indicate the reason of the exception frame 
 
    Error code 

 

Details 

 

$01   

 

Function code not allowed. Only the function code $03 or $04 are used by the INL100-150  

 

 

 

 

(register reading function). 

 
 

$02   

 

Data address not allowed 

 

 

 

$04   

 

Slave busy. The internal communication slot is not in connection with the measure part. 

 
RS485 MODBUS communication 

 

          

    MSW 

                                     LSW 

 

byte 1   

    byte 2 

   

  byte 3 

 

byte 4 

 
31 

 

24  23   

 

    16  15  

           8  7 

 

       0    

       Byte 1 

 

    Byte 2 

 

 

 

15  

    MSB   

  8  7 

      LSB      

    0 

Содержание IPL36L

Страница 1: ...meter LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Telefax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual at www...

Страница 2: ...nfiguration p8 5 Relays threshold setting visualization p8 RS232 LINK SETTING p9 TERMINAL MODE p10 1 Visualization p10 2 Configuration p10 2 1 Method p10 2 1 1 Menu selection p10 2 1 2 Parameter selec...

Страница 3: ...Visualization At power on the device displays briefly its actual revision number It s a message of the form r x y where x is the hardware revision and y the software revision Then it displays the cur...

Страница 4: ...current input 200 mV 200 A for the external shunt current input default shunt sensitivity is 1 A mV 4000 mV for the Hall sensor current input default configured caliber is 100 A The inputs configurati...

Страница 5: ...ose the three phases mode or the no button to select the previous choice PT RATIO Push the yes button to access the PT ration setting 0 001 to 106 or the no button to go to the next rubric CT RATIO Pu...

Страница 6: ...ergy count no to deactivate it PULSE WEIGHT Push the yes button to access the counting pulse weight parameter 0 01 kWh minimum RELAY 2 Push the yes button to access to the relay 2 configuration only w...

Страница 7: ...es button to access to the rubric Use the buttons to increase decrease the value and the button to validate it The output factory address is 1 BAUD RATE Push the yes button to access to the rubric Use...

Страница 8: ...measure mode without saving the new configuration 5 Setting or displaying the relays threshold If the threshold detection is activated pushing the button accesses to the threshold setting or displayi...

Страница 9: ...another communication port number COMx and re quires the reconfiguration of the HyperTerminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For later ve...

Страница 10: ...ration mode just press C key The message ConF is displayed in front 2 1 Method during the configuration different types of questions are displayed For each one several answers are possible You will fi...

Страница 11: ...eactivate the alarm on threshold overrun Threshold detection parameters are Monitored value voltage current frequency on IPL36 and IPL36L and active power reactive power apparent power power factor on...

Страница 12: ...tion Response time The limitation allows to bound the output signal swing to the configured output scales for any input signal swing over flow The response time allows to smooth the TRMS measure rippl...

Страница 13: ...play mode or N to choose the Y N YES fixed mode in kW kVAR kVA with 2 decimals 2 9 Special function This section allows you to lock the front face configuration access SPECIAL FUNCTION Press Y to acce...

Страница 14: ...Byte first word 1 exponent mantissa MSB word 2 mantissa Data in 32 bits integer signed or not Data send MSB first 4 bytes or 2 words long Data in 16 bits integer format for status of alarm R1 bit0 and...

Страница 15: ...ata The register address are the same as the table for MODBUS TCP This table lists the measures in 32 bits integer format and one 16 bits register for the alarms state address 18 The values given in t...

Страница 16: ...rge A network higher load can cause communication error due to the traffic The average response time to a read request is around 50ms 3 Data explanation All measures are accessible in reading mode Dat...

Страница 17: ...easures are at FFFFFFFF hexadecimal Register address in decimal Hexadecimal Designation Total words 4096 1000 Voltage V Word 1 1 Word 2 2 4098 1002 Current A Word 1 3 Word 2 4 4100 1004 Active Power W...

Страница 18: ...Multiply the values of powers by the PT ratio and the CT ratio or external shunt sensibility and divide the result by 10 000 Register address in decimal Hexadecimal Designation Total words 0 000 Volt...

Страница 19: ...ments of an IPL36 or IPL36L Click to refresh measures version number Tab for SNMP parameters Tab for password configuration IPL36 IPL36L There are no energy power power factor measurement 2 SNMP tab D...

Страница 20: ...re details The MIB file can be downloaded directly on the Web page of the device 3 Security tab Limit the web server access with a password This length of this password is up to 8 characters This char...

Страница 21: ...provide by LOREME and contain the firmware code in Intel HEX format Select the Transfer Send a text file in the HyperTerminal menu Select the directory and open the file The HyperTerminal program beg...

Страница 22: ...elays thyristor power groups Do not get closer within fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher t...

Страница 23: ...ption Analogical output mA terminals analog analog no jumper Analogical output V terminals analog analog need jumper between terminals analog 500 High voltage input terminals 600 V 0V Low voltage inpu...

Страница 24: ...terminals L N Relay 1 terminals common C1 rest R1 work T1 Relay 2 terminals common C2 rest R2 work T2 High voltage input terminals 600 V 0V Low voltage input terminals 150 V 0V Current input terminal...

Отзывы: