SOMMAIRE
E 17
4) Tables of measures
4.1) 32 bits floating format measures
This table lists the measures in 32 bits floating point format and 16 bits register for alarm status (address 4108).
Remark:
For an IPL36L, the Powers and Power Factor measures are at FFFFFFFF hexadecimal.
Register address in decimal
(Hexadecimal)
Designation
Total
words
4096 ($1000)
Voltage (V)
Word 1
1
Word 2
2
4098 ($1002)
Current (A)
Word 1
3
Word 2
4
4100 ($1004)
Active Power (W)
Word 1
5
Word 2
6
4102 ($1006)
Reactive Power (VAR)
Word 1
7
Word 2
8
4104 ($1008)
Apparent Power (VA)
Word 1
9
Word 2
10
4106 ($100A)
Power Factor
Word 1
11
Word 2
12
4108 ($100C)
Alarms (b0: AL1, b1: AL2)
Word 1
13
4109 ($100D)
Frequency
Word 1
14
Word 2
15