©2016 Acuity Brands Lighting, Inc.
All Rights Reserved.
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
Part Number: IN-379 Rev F
Revision Date: 11/19/18
Installation Instructions
RSX LED
4. The luminaire is supplied with a variety of slots to
align with existing pole mounting drill patterns. The top
hole of the luminaire arm has a key hole slot.
Place the luminaire onto the top bolt by passing the head
through the key slot and resting the luminaire down securely
in place (See Figure 3).
WARNING: THE LUMINAIRE IS NOT COMPLETELY
LOCKED DOWN YET. SPECIAL CARE MUST BE TAKEN
TO AVOID JARRING THE LUMINAIRE FROM ITS REST-
ING POINT, OTHERWISE THE LUMINAIRE COULD
FALL AND CAUSE SERIOUS INJURY OR DEATH!
Ensure the luminaire is resting securely on the top bolt. Snug
the bolt but do not completely tighten. Thread the second
bolt through the arm slot and into the available threaded hole
of the mounting bar (See Figure 4).
5. The luminaire is supplied with a clearance slot in the
back to allow wires to be pulled into the pole on existing hole
patterns. Insert the wires through the clearance slot shown in
Figure 5 and pull them into the pole.
6. Ensure luminaire is straight/level making sure that no wires
are pinched, tighten the two bolts with a 3/8 socket to 20-30
ft-lbs (overtightening can damage components and void war-
ranties). Make sure that wires are not pinched and tuck excess
wire up into the luminaire mounting area.
7. Reinstall the SPA Cover that was removed, tighten the two
captive screws with the 9/64 Allen wrench to 18-20 in-lbs
(overtighten can cause thread stripping and void all warran-
ties)(See Figure 6).
8. Make wire connections in the pole, observing proper volt-
age and polarity. Connect green ground wire from the fixture
to the field ground wire. Secure wires; push back into pole
and replace pole cap.
First Bolt
Key
Hole Slot
location
Figure 3
Figure 4
Figure 5
Figure 6
Second Bolt
SPA Cover
Mounting