SFA-5000 • SFA-10000 DeviceNet
and then execute the preset setting, the
system saves the current encoder position in the
follows that the transmitted value and the
read
position
= 0; in other words, the value set next to the
attribute is paired with the current position of the encoder as you
wish.
For example, let's assume that the value “50” is set next to the
attribute and you execute the preset setting when the encoder position is
“1000”. In other words, you want to receive the value “50” when the encoder
reaches the position “1000”.
We will obtain the following information sequence:
Transmitted value
=
read position
(=”1000”) = 50.
The following transmitted value will be:
Transmitted value
=
read position
(=”1000”) = 51.
And so on.
NOTE
If the scaling function is disabled (see the
must be less than or equal to the “
Total
hardware resolution
” - 1 (
8 Physical resolution/revolution
- 1).
If the scaling function is enabled (see the
must be less than or equal to the
- 1.
WARNING
attribute and perform the preset
operation every time you change the
and/or
attributes).
8 Physical resolution/revolution
WARNING
This attribute is active only if the
”=0”; otherwise it is ignored and the system uses the custom values (
) to calculate the position
information.
MAN SFA_5000_10000_FD E 1.0.odt Quick reference (using RSNetWorx)44 of 88