5.8.- PROGRAM
The unit is made up of stages with different powers.
The base power (value 1) will be that of the stage
with the lowest power. The powers of all the other
stages will depend on the power of the first stage.
Example:
Program 1�1�1�1
, all the stages have the same
power as the first one.
Program 1�2�4�4
, the second stage has twice the
power and the next ones have four times the power
of the first one. (
See
“4.1.4 Regulation program”
)
When configuring the program, remember that the subsequent stage cannot be lower than the
prior stage, and that the first stage is always 1.
Also program the system that controls the connection sequence of the different stages, where:
FCP
, operation following the
FCP
(
“4.1.3 FCP System (FAST Computerized
Program)”
)
TOTAL
, total operation where all the steps are connected or disconnected at the same
time, without following a sequence; This operation is faster than the
FCP
.
SIM
, no operation, the unit stays in simulation mode
(1)
.
(1)
In
SIM
mode, the measurement screens simulate the outputs that the unit would connect or
disconnect, but it doesn't actually do so. To avoid confusion, on the measurement screens the
name of the screen is switched with the literal
M
o
d
e
S
im
.
Press the
key to enter editing mode. It is identified by the
symbol and the blinking
of the digits to be modified.
The
key increases the digit value.
The
key decreases the digit value.
The
key skips to the previous digit.
The
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Minimum value:
1.1.1.1
Maximum value:
1.9.9.9
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
“5.27.-
SIMULATION SCREEN”
.
81
Instruction Manual
Controller MASTER control VAR FAST