Connection type:
3U�3C:
3 voltages and 3 currents
�
3U�1C:
3 voltages and 1 current
�
2U�1U:
2 voltages and 1 current
�
Phase
Cos
φ III
L: Inductive / C: capacitive
+: consumed / -: generated
Press the
key to switch to the next screen of results.
Press the
key to exit the results screen.
No� steps detected
Program
C/K factor
Cos
φ III
L: Inductive / C: capacitive
+: consumed / -: generated
Press the
key to switch to the previous screen of results.
Press the
key to exit the results screen.
If any errors occur during the execution of the Plug&Play function, the process will be aborted
and the errors will be displayed on the screen. When a parameter has been calculated correctly
before the error is detected, it will be displayed on the previously assigned line. The errors that
can occur in the Plug&Play function are shown in
Table 40
.
Table 40: Code of Plug&Play errors�
Code
Description
P00
There are three possible causes that can prevent the Plug&Play process
from starting:
- Some stages are cancelled by the leakage current alarm.
- Some stages are forced in the configuration
"5.12.- STATUS OF THE
STAGES”.
P01
Error when searching for the Connection Type. See connection diagrams.
P02
Phase not found. Cosine out of range (between 0.62 and 0.99 inductive).
P03
Unstable measurement. Load changes during the process.
73
Instruction Manual
Controller MASTER control VAR FAST