5.2.- CURRENT TRANSFORMATION RATIO
The primary and secondary value of the current
transformer is configured in this point.
Press the
key to enter editing mode. It is
identified by the
symbol and the blinking of
the digits to be modified.
The
key increases the digit value or shows the next option.
The
key decreases the digit value or shows the next option.
The
key skips to the previous digit.
The
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Current primary:
Maximum
value:
9999.
Minimum
value:
1.
Current secondary:
Possible
values:
1 or
5.
Maximum possible current ratio:
2500.
NB:
The current ratio is the ratio between the current primary and secondary.
Maximum value of the current ratio x the voltage ratio:
200000.
If the value entered is lower than the minimum value or higher than the maximum value,
the backlight of the display flashes and the value entered is replaced with the minimum or
maximum value, or with the last value validated.
Press the
key to access the next programming step
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
“5.27.-
SIMULATION SCREEN”
.
75
Instruction Manual
Controller MASTER control VAR FAST