Table 24:Modbus memory map: programming variables (Table 10)
C/K factor
Configuration variable
Address
Valid data margin
Default value
C/K factor
1138
0 - 100 (Value x 100)
100
Table 25:Modbus memory map: programming variables (Table 11)
Program
Configuration variable
Address
Valid data margin
Default value
Program
1139
1111-1999
1111
Operation type
113A
0(FCP), 1(Total), 2(Sim)
0
Table 26:Modbus memory map: programming variables (Table 12)
No� of stages
Configuration variable Address
Valid data margin
Default value
No. of stages
113B
0-6 (Controller MASTER control VAR FAST 6)
0-12 (Controller MASTER control VAR FAST 12)
6
12
Table 27:Modbus memory map: programming variables (Table 13)
Connection and reconnection time
Configuration variable
Address
Valid data margin
Default value
Connection time
113C
0-999 network cycles
10
Reconnection time
113D
0-999 network cycles
50
Table 28:Modbus memory map: programming variables (Table 14)
Alarm: Voltage THD
Configuration variable
Address
Valid data margin
Default value
Low Value
1140
0 - 100 %
5
Hi Value
1141
0 - 100 %
10
Table 29:Modbus memory map: programming variables (Table 15)
Alarm: Current x I THD
Configuration variable
Address
Valid data margin
Default value
Low Value
1142
0 - 100 %
4
Hi Value
1143
0 - 100 %
5
Table 30:Modbus memory map: programming variables (Table 16)
Alarm: Temperature
Configuration variable
Address
Valid data margin
Default value
Low Value
1144
0 - 80 ºC
55
Hi Value
1145
0 - 80 ºC
70
Table 31:Modbus memory map: programming variables (Table 17)
Alarm: Leakage Current
Configuration variable
Address
Valid data margin
Default value
Search for the responsible stage
1146
0 (OFF), 1 (ON)
0
Value
1147
10 - 1000 mA
300
Stages enabled
1148
0 (No), 1 (Yes)
0
Table 32:Modbus memory map: programming variables (Table 18)
Alarm: Cos
φ
Configuration variable
Address
Valid data margin
Default value
Value of Cos φ
1149
80 -100 (Value x 100)
95
Current value
114A
0 - 9999 A
20
Type of Cos φ
114B
0 (Capacitive), 1 (Inductive)
1
66
Controller MASTER control VAR FAST
Instruction Manual