![Lifasa MASTER control Var Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/lifasa/master-control-var/master-control-var_instruction-manual_1907739067.webp)
Table 33:Modbus memory map: programming variables (Table 19)
Alarm: Fan
Configuration variable
Address
Valid data margin
Default value
Value
114C
0 - 80 ºC
35
Enabled
114D
0 (OFF), 1 (ON)
0
Table 34:Modbus memory map: programming variables (Table 20)
Alarm: Voltage
Configuration variable
Address
Valid data margin
Default value
Overvoltage value
114E-114F
0-99999
440
No Voltage Value
1150-1151
0-99999
360
Table 35:Modbus memory map: programming variables (Table 21)
No� of operations
Configuration variable
Address
Valid data margin
Default value
No. of operations
1152-1153
1-99999
5000
Table 36:Modbus memory map: programming variables (Table 22)
Enabling alarms
Configuration variable
Address
Valid data margin
Default value
Enable Alarm E01
1155
0 (OFF), 1 (ON)
1
Enable Alarm E02
1156
1
Enable Alarm E03
1157
1
Enable Alarm E04
1158
1
Enable Alarm E05
1159
0
Enable Alarm E06
115A
0
Enable Alarm E07
115B
0
Enable Alarm E08
115C
0
Enable Alarm E09
115D
0
Enable Alarm E10
115E
0
Enable Alarm E11
115F
0
Enable Alarm E12
1160
0
Enable Alarm E13
1161
0
Enable Alarm E14
1162
0
Enable Alarm E15
1163
0
Enable Alarm E16
1164
0
Enable Alarm E17
1165
0
67
Instruction Manual