3�5�5�- 2 VOLTAGES AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR FAST 6
MODEL�
Connection type:
2U
.
1C
V
LN
I
L2
S1
L1
L2
L3
N
V
L1
V
L2
V
L3
S1
S2
P1
P2
S1
S1
S2
S2
S2
I
L3
I
L1
A1 A2
Power Supply
COM 1 2 3 4 5 6
COM ACT C1...C6
Power Supply
Figure 7: 2 voltages and 1 current, Controller MASTER control VAR FAST 6 model�
Note:
If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section
"5�6�- PHASE CONNECTION”
Note:
In this type of connection, the Neutral connection is not necessary.
Note:
In this type of connection, the current transformer must be connected to the I
L1
termi-
nals, and the two voltages must be connected to V
L1
and V
L2
.
18
Controller MASTER control VAR FAST
Instruction Manual