AC Module System Installation Manual
Copyright © 2020 LG Electronics.
All Rights Reserved.
38
Rev. 1.0
3-12 Connecting Array of AC Modules to Distribution Panel
Before connecting general AC cable from the AC junction box to distribution panel, adhere to the following items:
•
To prevent the danger of electric shock, check again if the circuit breaker is turned off.
•
LG does not provide separate general AC wiring coming from the distribution panel to an AC junction box.
•
Undertake the Installation works using certified parts and tools.
•
Do not put any liquid or metal into connectors, cables, or end caps. There is a danger of electric shock.
•
Do not use any damaged cables.
•
Do not use general AC conductors smaller than size of AC cables provided by LG.
•
To prevent property damage or danger to human life by fire or explosion, do not connect any load
between AC module and the circuit breaker.
• To prevent the danger of electric shock, make sure to turn off the circuit breaker.
Each conductor can be identified by the color of wire.
N.C. means ‘No Connection’.
Notice
Extension cable (serviceable as a transition cable)
The color of wire inside the cable
Male end cap
Female extension
cable connector
Male extension cable
connector
Female end cap
1600 mm, 63 in.
L1
L2
N
L1 (Black)
L2 (Red)
Neutral (White)
N.C.
End caps are Initially paired with connectors.
L1
L2
N
N.C.