Test Run
74
Hydro Kit
If
Hydro Kit
operates not properly or it does not start operation, please check following list.
Troubleshooting
Error No.
Error Type
Main Reasons
01
Air temperature sensor error
Air temperature sensor disconnection or short
circuit
02
Gas side temperature sensor error
Gas side temperature sensor disconnection or
short circuit
03
No communication between wired
remote controller & indoor unit
The remote controller does not receive the signal
from indoor unit during specific time
05
Indoor unit & outdoor unit
communication error
No signal communication between indoor unit &
outdoor unit
06
Liquid side temperature sensor error
Liquid side temperature sensor disconnection or
short circuit
08
Water tank temperature sensor error
Water tank temperature sensor disconnection or
short circuit
09
Indoor unit EEPROM error
Communication between the micro-processor &
the EEPROM / Error due to EEPROM damage
11
Indoor unit & inverter PCB
communication error
No signal communication between indoor unit &
inverter PCB
12
Inverter PCB error
Error occurrence in inverter PCB
13
Solar thermal temperature sensor
error
Solar thermal temperature sensor disconnection
or short circuit
14
Flow switch error
Abnormal working of flow switch
15
Water pipe overheated
Water outlet temperature is above 85 ℃ (185 °F)
16
Water inlet & outlet temperature
sensor error
Water inlet & outlet temperature sensor
disconnection or short circuit simultaneously
17
Water inlet temperature sensor error
Water inlet temperature sensor disconnection or
short circuit
18
Water outlet temperature sensor
error
Water outlet temperature sensor disconnection or
short circuit
187
Hydro-Kit P.HEX bursting error
Inlet water temperature is below 5 degree or
water temperature error during defrosting
operation.